242
Appendix 9
Comparison with NZ2GF2B-60AD4
Appendix 9.1
Comparison of performance specifications
The following table shows the differences in the performance specifications between the NZ2GF2BN-60AD4 and the
NZ2GF2B-60AD4.
Appendix 9.2
Functional comparison
The following table shows the differences in the functions between the NZ2GF2BN-60AD4 and the NZ2GF2B-60AD4.
Item
NZ2GF2BN-60AD4
NZ2GF2B-60AD4
Accuracy
Ambient temperature (25
±
5
)
±
0.1%
±
0.2%
Ambient temperature (0 to
55
)
±
0.2%
Conversion speed
• 100
μ
s/channel
• 400
μ
s/channel
• 1ms/channel
• 400
μ
s/channel
• 1ms/channel
External power supply
24VDC (20.4 to 28.8VDC)
Inrush current: 36.5A, 1ms or lower
Current consumption: 210mA
24VDC (20.4 to 28.8VDC)
Inrush current: 31.2A (for 1.5ms or shorter)
Current consumption: 230mA
Item
NZ2GF2BN-60AD4
NZ2GF2B-60AD4
Conversion speed switch function
Allows switching into the following conversion
speeds:
• 100
μ
s/channel
• 400
μ
s/channel
• 1ms/channel
Allows switching into the following conversion
speeds:
• 400
μ
s/channel
• 1ms/channel
Speed switching of the trigger conversion function
Allows switching between 100
μ
s/channel and
400
μ
s/channel
Not available
Conversion speed switching of the CC-Link IE
Field Network synchronous communication
function
Allows switching between 100
μ
s/channel and
400
μ
s/channel
Not available
Support for extension modules
The following extension modules can be mounted:
• Extension input module
• Extension output module
• Extension A/D converter module
• Extension D/A converter module
The following extension modules can be mounted:
• Extension input module
• Extension output module