213
APPX
A
Appendix 3 Details of Re
mote Buffer Me
mory
(10)Digital output HOLD/CLEAR setting
Set the output HOLD/CLEAR of the extension output module.
For the output HOLD/CLEAR setting function, refer to the following:
CC-Link IE Field Network Remote I/O Module User's Manual
(a) Enabling the setting
Turn on and off Initial data setting request flag (RY9) to enable the setting.
(b) Default value
The default value is CLEAR (0H).
(c) Remote buffer memory address
The remote buffer memory address of this area is as follows:
●
When no extension output module is connected, the setting of Digital output HOLD/CLEAR setting (address: 0011H) is
ignored.
●
Setting data other than the above results in operation with the set value of the lower 1 bit.
(11)A/D conversion enable/disable setting
Set whether to enable or disable A/D conversion for each channel.
(a) Enabling the setting
Turn on and off Initial data setting request flag (RY9) to enable the setting.
(b) Default value
The default value is Enabled (0) for all channels.
(c) Remote buffer memory address
The remote buffer memory addresses of this area are as follows:
Output HOLD/CLEAR setting
Setting value
CLEAR
0H
HOLD
1H
Remote buffer memory name
Main A/D converter module
Extension A/D converter module
Digital output HOLD/CLEAR setting
0011H
Remote buffer memory name
Main A/D converter module
Extension A/D converter module
CH1
CH2
CH3
CH4
CH1
CH2
CH3
CH4
A/D conversion enable/disable setting
0102H
0202H
0
0
0
0
0
0
0
0
0
0
0
CH1
CH2
CH3
CH4
0
b15 b14 b13 b12 b11 b10
b9
b8
b7
b6
b5
b0
b1
b2
b3
b4
0: A/D conversion enabled
1: A/D conversion disabled
The values of b4 to b15 are fixed to 0.