152
8.19
CC-Link IE Field Network Diagnostic Function
This function can be used by accessing the engineering tool connected to the CPU module, enabling the detection of a
network error.
(1) How to use the function
The following instructions assume the use of GX Works2 as the engineering tool.
1.
Establish a connection between GX Works2 and the CPU module.
2.
Go to the menu of GX Works2 and start up the CC-Link IE Field Network diagnostics.
[Diagnostics]
[CC IE Field Diagnostics]
Item to be diagnosed
Description
Reference
Network configuration and error
condition
Allows the condition of the CC-Link IE Field Network to be checked.
If an error or a warning occurs in the A/D converter module, an icon appears to show the
status of the station.
User's manual for the
master/local module
used
Display of selected-station
status and error details
The communication status of the station selected in "Networks Status" can be checked.
Communication Test
The transient communication route and whether the communication is established from
the connected station to the destination station can be checked.
IP Communication Test
The reaching time and the route of the IP communication from the connected station to
the target station can be checked.
Cable Test
The cable status between the connected station and the destination station can be
checked.
Link Start/Stop
The network data link can be started and stopped.
Network Event History
The history of various events that occurred in the network can be checked.
Reserved Station Function
Enable
A reservation for a station can be temporarily cancelled, and the cancellation can be
disabled. Also, the station numbers for the modules set as reserved stations can be
checked on a list.
Enable/Disable Ignore Station
Errors
A station not set as an error invalid station can be temporarily set as an error invalid
station, and the error invalid station setting can be disabled. Also, the station numbers for
the modules set as (temporarily) error ignore stations can be checked on a list.
System Monitor
The system monitor on the selected station is activated and the status of the module can
be checked.
This function is unavailable for the A/D converter module.
Remote Operation
The selected station can be reset through the remote operation.
Page 153, Section 8.19
(1) (a)
1
3
4
5
2
Summary of Contents for NZ2EX2B-60AD4
Page 2: ......
Page 49: ...47 CHAPTER 4 PROCEDURES BEFORE OPERATION 4 Memo ...
Page 156: ...154 3 In the dialog box that appears shown below click button ...
Page 169: ...167 CHAPTER 10 MAINTENANCE AND INSPECTION 10 Memo ...
Page 253: ......