CHAPTER 8 FUNCTIONS
8
8.10 Alert Output
Function
(Process Alarm)
(6) Setting procedure
The setting procedure for the main A/D converter module is as follows:
1.
Set "Method selection" to "Parameter write".
"CC IE Field Configuration" window
Select the main A/D converter module from "List of stations"
[CC IE Field Configuration]
[Online]
[Parameter Processing of Slave Station]
2.
In "Basic module parameter", set "CH
A/D conversion enable/disable setting" to "0: Enable".
3.
In "Basic module parameter", set "CH
Alert output setting" to "0: Enable".
4.
In "Basic module parameter", specify the values for "CH
; Process alarm upper upper limit
value", "CH
Process alarm upper lower limit value", "CH
Process alarm lower upper limit
value", and "CH
Process alarm lower lower limit value".
●
Alert output function must meet the following condition:
Process alarm upper upper limit value
≥
Process alarm upper lower limit value
≥
Process alarm lower upper limit value
≥
Process alarm lower lower limit value
●
For the extension A/D converter module, make the settings for each item of "Ext. module 1_Module parameter".
Item
Setting range
CH
Process alarm upper upper limit value
-32768 to 32767
CH
Process alarm upper lower limit value
CH
Process alarm lower upper limit value
CH
Process alarm lower lower limit value