214
(12)Range setting
Set the input range for each channel.
(a) Enabling the setting
Turn on and off Initial data setting request flag (RY9) to enable the setting.
(b) Default value
The default value is 4 to 20mA (0H).
(c) Remote buffer memory address
The remote buffer memory addresses of this area are as follows:
Setting data other than the above results in the error code (010
H or 110
H) being stored in Latest error code (RWr0),
Error flag (RXA) turning on, and the ERR. LED turning on. A channel where data other than the above is set operates in the
same way as when the A/D conversion is disabled.
Input range
Setting value
Main A/D converter module
Extension A/D converter module
4 to 20mA
0H
0H
0 to 20mA
1H
1H
1 to 5V
2H
2H
0 to 5V
3H
3H
-10 to 10V
4H
4H
User range setting 1
5H
User range setting 2
6H
Remote buffer memory name
Main A/D converter module
Extension A/D converter module
CH1
CH2
CH3
CH4
CH1
CH2
CH3
CH4
Range setting
0103H
0203H
b15
to
b12 b11
to
b8
b7
to
b0
to
b3
b4
CH1
CH2
CH3
CH4
Summary of Contents for NZ2EX2B-60AD4
Page 2: ......
Page 49: ...47 CHAPTER 4 PROCEDURES BEFORE OPERATION 4 Memo ...
Page 156: ...154 3 In the dialog box that appears shown below click button ...
Page 169: ...167 CHAPTER 10 MAINTENANCE AND INSPECTION 10 Memo ...
Page 253: ......