177
CHAPTER 11 TROUBLESHOOTING
11
11.2 Er
ror
Code List
(2) Error code list (D000H to DFFFH (D529H and D52BH excluded))
While any of these errors occurs, the ERR. LED does not turn on. Based on the behavior of the D LINK LED at
the occurrence of an error, the errors are classified into two types, each of which requires different
troubleshooting.
(a) Communication errors where the D LINK LED flashes or turns off
This type of communication error results in the D LINK LED flashing or being turned off. Troubleshoot the
problem with the CC-Link IE Field Network diagnostics. (
(b) Communication errors where the D LINK LED does not change
This type of communication error results in no change of the D LINK LED. These errors are not shown in CC-
Link IE Field Network diagnostics because they are automatically recovered after the occurrence.
Troubleshooting them requires the error history to be read out. (
Page 168, Section 11.1 (1))
For two or more errors, only the latest error code is stored in Latest error code (RWr0) or Latest warning code (RWr1).
The errors that have occurred in the past can be checked in the error history of the engineering tool.
For the error history, refer to the following:
• Checking by executing a command of the slave station (
• Error history data
(
Error code
(hexadecimal)
Error name
Description and cause
Action
D0E0H
Station type mismatch
The network parameters are
incorrect or out of the range.
In the network configuration settings of the master station, change
the station type of the module to the remote device station.
D0E1H
Own station set to reserved
station
The network parameters are
incorrect or out of the range.
• In the network configuration settings of the master station, cancel
the reserved station specification.
• Change the station number of the module to a station number that
is not specified as a reserved station.
D0E2H
Own station’s station number
duplication error
The settings of the station
number switch are invalid or out
of the range.
• Change the station number avoiding duplication of the station
number with other stations.
• After taking the above action, power off and on or reset all the
stations where a own station’s station number error has been
detected.
D0E3H
Own station’s station number
out-of-range
The network parameters are
incorrect or out of the range.
Add the station information of the module to the network
configuration settings of the master station.
D72AH
Station number switch out-of-
range (a value other than 1 to
120)
A station number out of the
range has been set.
Set the station number within the allowable range.
Error code
(hexadecimal)
Error name
Description and cause
Action
D217H
Transient data request
command error
The transient data request
command is incorrect.
Correct the request command at the transient request source, and
execute the command again.
D2A0H
Receive buffer full error
There is an overload of the
received transient data.
• Check the network status using CC-Link IE Field Network
diagnostics of the engineering tool to take the appropriate action.
• If the received transient data of the target station is overloaded,
leave the send source for a certain time and try to send the data.
D2A3H
Transient data length error
The received transient data is
incorrect.
Correct the number of data (frame length) at the request source, and
retry the execution.
DF01H
Received transient split error
The received transient data is
split.
Set the transient data size that the module can accomodate, and
modify the transient data to the one that is not split. Then send it
again.