215
APPX
A
Appendix 3 Details of Re
mote Buffer Me
mory
(13)Averaging process specification
This area is used for setting sampling processing or selecting the type of averaging processing for each channel.
There are the following types of averaging processing: time average, count average, and moving average.
(a) Enabling the setting
Turn on and off Initial data setting request flag (RY9) to enable the setting.
(b) Default value
The default value is Sampling processing (0H) for all channels.
(c) Remote buffer memory address
The remote buffer memory addresses of this area are as follows:
●
In the trigger conversion mode or synchronous communication mode, the setting of Averaging process setting (address:
0104H and 0204H) is ignored and the sampling processing is performed.
●
A channel to which a value out of the above range is written operates with the sampling processing.
Processing method
Setting value
Sampling processing
0H
Time average
1H
Count average
2H
Moving average
3H
Remote buffer memory name
Main A/D converter module
Extension A/D converter module
CH1
CH2
CH3
CH4
CH1
CH2
CH3
CH4
Averaging process specification
0104H
0204H
b15
to
b12 b11
to
b8
b7
to
b0
to
b3
b4
CH1
CH2
CH3
CH4