221
APPX
A
Appendix 3 Details of Re
mote Buffer Me
mory
(21)CH
Maximum value, CH
Minimum value
The maximum and minimum values of converted digital operation value are stored as signed 16-bit binary.
See below for reset.
• Turning on and off Maximum value/minimum value reset request (RY1D) of the main A/D converter module
results in CH
Maximum value and CH
Minimum value of the main A/D converter module being updated
to the current value.
• Turning on and off Maximum value/minimum value reset request (RY2D) of the extension A/D converter
module results in CH
Maximum value and CH
Minimum value of the extension A/D converter module
being updated to the current value.
• Turning on and off Initial data setting request flag (RY9) results in CH
Maximum value and CH
Minimum
value of both the main A/D converter module and the extension A/D converter module being updated to the
current value.
(a) Remote buffer memory address
The remote buffer memory addresses of this area are as follows:
●
With the averaging processing specified, the maximum and minimum values are updated per averaging process cycle;
otherwise, updated per sampling cycle.
●
With the following functions used, values computed by each function are stored in the maximum value and the minimum
value:
• Digital clipping function
• Scaling function
• Shift function
• Difference conversion function
(22)Extension module identification code
The identification code for a connected extension module is stored.
If the extension A/D converter module is connected, 2111H is stored.
For the identification code for extension modules other than the extension A/D converter module, refer to the
following:
Manual including the description of the extension module used
(a) Remote buffer memory address
The remote buffer memory address of this area is as follows:
Remote buffer memory name
Main A/D converter module
Extension A/D converter module
CH1
CH2
CH3
CH4
CH1
CH2
CH3
CH4
CH
Maximum value
0601H
0603H
0605H
0607H
0701H
0703H
0705H
0707H
CH
Minimum value
0602H
0604H
0606H
0608H
0702H
0704H
0706H
0708H
Remote buffer memory name
Main A/D converter module
Extension A/D converter module
Extension module identification code
0700H
Summary of Contents for NZ2EX2B-60AD4
Page 2: ......
Page 49: ...47 CHAPTER 4 PROCEDURES BEFORE OPERATION 4 Memo ...
Page 156: ...154 3 In the dialog box that appears shown below click button ...
Page 169: ...167 CHAPTER 10 MAINTENANCE AND INSPECTION 10 Memo ...
Page 253: ......