(17)CH
Process alarm lower lower limit value, CH
Process alarm lower upper
limit value, CH
Process alarm upper lower limit value, CH
Process alarm
upper upper limit value
Set the range of digital operation value for each channel.
For details on Alert output function (process alarm), refer to the following:
• Alert Output Function (Process Alarm) (
(a) Setting range
• Setting range is -32768 to 32767.
• The settings consist of the four items: process alarm upper upper limit value, process alarm upper lower
limit value, process alarm lower upper limit value, and process alarm lower lower limit value.
(b) Enabling the setting
Turn on and off Initial data setting request flag (RY9) to enable the setting.
(c) Default value
The default value is 0.
(d) Remote buffer memory address
The remote buffer memory addresses of this area are as follows:
●
An error occurs in a channel with a set value out of the range above or a set value not meeting the following condition:
Process alarm upper upper limit value
≥
Process alarm upper lower limit value
≥
Process alarm lower upper limit value
≥
Process alarm lower lower limit value. An error results in the error code (06
H or 16
H) being stored in Latest error
code (RWr0), Error flag (RXA) turning on, and the ERR. LED lighting up, resulting in operation just before the error.
●
By default, 0 is set and so change the set value.
●
When the following functions are used, alert targets are digital operation values that reflect the operations of each
function. Set values considering operation results of each function.
• Digital clipping function
• Scaling function
• Shift function
• Difference conversion function
Remote buffer memory name
Main A/D converter module
Extension A/D converter module
CH1
CH2
CH3
CH4
CH1
CH2
CH3
CH4
CH
Process alarm lower lower limit value
010FH
0113H
0117H
011BH
020FH
0213H
0217H
021BH
CH
Process alarm lower upper limit value
0110H
0114H
0118H
011CH
0210H
0214H
0218H
021CH
CH
Process alarm upper lower limit value
0111H
0115H
0119H
011DH
0211H
0215H
0219H
021DH
CH
Process alarm upper upper limit value
0112H
0116H
011AH
011EH
0212H
0216H
021AH
021EH