(b) Setting procedure
1.
Set "Method selection" to "Parameter write".
"CC IE Field Configuration" window
Select a main A/D converter module from "List of stations"
[CC IE Field Configuration]
[Online]
[Parameter Processing of Slave Station]
2.
In "Basic module parameter", set "CH
A/D conversion enable/disable setting" to "0: Enable".
3.
In "Basic module parameter", set "CH
Alert output setting" to "0: Enable".
4.
In "Basic module parameter", specify the values for "CH
; Process alarm upper upper limit
value", "CH
Process alarm upper lower limit value", "CH
Process alarm lower upper limit
value", and "CH
Process alarm lower lower limit value".
5.
In "Basic module parameter", set "Alert output signal assignment" to 0x002A. (The string 2A is
derived from RY2A.)
●
Signals other than remote I/O signals assigned to the external module cannot be set with the external signal assignment
function.
Such a setting would result in the error code (017
H) being stored in Latest error code (RWr0), Error flag (RXA) turning
on, and the ERR. LED turning on.
●
Multiple remote I/O signals of the main module cannot be assigned to a remote output signal of the extension module.
If the above is set, the error code (0180H) is stored in Latest error code (RWr0), Error flag (RXA) turns on, and the ERR.
LED turns on.
●
The external signal assignment function cannot be used together with the digital output HOLD/CLEAR function.
When "Digital output HOLD/CLEAR setting" is set to "1: HOLD", the setting is ignored and the A/D converter module
operates with "0: CLEAR" set.