52
6. R.V. coil control
Heating · · · · · ON
Cooling · · · · · OFF
Dry · · · · · · · · OFF
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
ON
OFF
ON
OFF
ON
OFF
Compressor
R.V. coil
Outdoor fan
(COOL / DRY)
(HEAT)
5 seconds
5 seconds
ON
OFF
ON
OFF
ON
OFF
NOTE
●
When the indoor coil thermistor reads above 18°C, indoor fan operates at Very Low for 30 seconds.
●
When the indoor coil thermistor reads 18°C or less, the indoor fan stops.
(3) Defrosting time chart
Defrost thermistor RT61
-3
:
or more
-3
:
or less
Compressor
X62
(R.V. coil)
Outdoor fan
Defrost
counter
Indoor fan
Indoor vane
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Horizontal
Set Position
Max 10 minutes
30 seconds
15 seconds
30 seconds
5 seconds
NOTE
Very Low
OB245 --2qxp 02.10.22 4:12 PM Page 52