59
Function
Symbol
Name
It improves the power factor of power supply.
It stabilizes the direct current voltage.
It measures the current of main power supply circuit.
It converts the alternating current voltage to direct current voltage.
It is combined with L to improve the power factor of power supply.
It generates three-phase alternating current and operates compressor.
It is combined with DS62 to improve the power factor of power supply.
It eliminates and absorbs the electrical noise.
It eliminates and absorbs the electrical noise.
It detects the current and protects the compressor and IPM.
It absorbs the rush current so not to run into the main power supply
circuit when the electricity is turned on.
It short-circuits the circuit to current-limiting resistor when the
compressor operates.
C61
C62
CT61
DS61
DS62
IPM
L
L61
L62
R61, R62
R64A
R64B
X64
POWER-FACTOR CAPACITOR
SMOOTHING CAPACITOR
CURRENT TRANSFORMER
DIODE STACK
DIODE STACK
INTELLIGENT POWER MODULE
REACTOR
COMMON MODE CHOKE COIL
COMMON MODE CHOKE COIL
CURRENT-DETECTING RESISTOR
CURRENT-LIMITING RESISTOR
RELAY
1Hr
Time: T
Maximum
frequency
Frequency
Rating or under rating frequency
w
The maximum frequency in COOL mode varies according to operation hours as shown below.
w
However, it is under rating frequency when indoor fan speed is set to MANUAL Low or AUTO Low.
Minimum
frequency
Maximum
frequency
Minimum
frequency
Maximum
frequency
15
COOL
HEAT
120
15
120
DRY
84
2. Control by the difference between the room temperature and the set temperature
The frequency is controlled by the difference between the room temperature and the set temperature.
(1) Frequency when the unit starts operation
9-23. Operational frequency control of outdoor unit
1. Outline
The operational frequency is as following:
First, the target operational frequency is set based on the difference between the room temperature and the set temper-
ature.
Second, the target operational frequency is regulated by discharge temperature protection, high pressure protection,
electric current protection and overload protection and also by the maximum/minimum frequency.
Maximum/minimum frequency in each operation mode.