81
Check of power supply
M
Inverter does not work.
Check of thermal fuse
N
Check of rush current limiting circuit
O
Outdoor unit does not operate at all or stops immediately due to over current.
Replace the current limiting resistor (R64).
Disconnect the connector
between compressor and
transistor module.
Turn ON power supply to indoor
unit and press EMERGENCY
OPERATION switch.
Turn OFF the
power supply.
Replace the
thermal fuse (F12).
Check the electric
parts in main circuit.
Replace the outdoor
electronic control P.C.
board.
Ok
When the current limiting resistor is open, the rush current limiting relay may not be working properly.
Therefore confirm the limiting resistor works properly after replacing it.
Three minutes after
power ON, is there
voltage of approx. 230V
AC between outdoor
terminal block
2
and
N
?
Is there voltage approx.
340V DC between TAB
64(-) and TAB 63(+)?
Dose LED light up or
flash?
Is resistance
∞
between the connector CN 201
1
on indoor
electronic control P.C. board and the terminal block
N
?
Outdoor terminal block
N
2
3
Yes
Yes
Yes
No
No
Yes
No
Does current limiting resistor (R64) detect 10
"
?
No
∞
Yes
CN201
Indoor electronic
control P.C. board
Press the
EMERGENCY
OPERATION switch.
Does the 52C work?
Repair wiring.
Replace the indoor
electronic control
P.C. board.
No
Yes
No
Ok
Ok
Start
Indoor/ outdoor
connecting
wire
OB245--3qxp 02.10.22 4:15 PM Page 81