Check of expansion valve (LEV)
P
Heating/Cooling does not operate.
Replace the
LEV coil.
Replace the LEV.
With remote controller set toward the indoor unit,
press OPERATE/ STOP(ON/ OFF)
button and confirm one beep tone.
Replace the outdoor
electronic control P.C.
board.
LEV operates in full-opening
direction.
Is LEV coil properly fixed to
the body?
Ok
Do you hear LEV "click,
click·······"?
Do you touch LEV and
feel it vibrate?
Do you hear LEV
"click, click·········"?
No
Yes
Yes
Yes
Yes
No
No
No
Properly fix LEV coil to
the body.
Ok
Confirm again that LEV
is operating.
Does the resistance have the
characteristics?
1
Press the EMERGENCY OPERATION switch.
2
Turn OFF the power supply.
3
Turn ON the power supply.