46
1 SERVO PARAMETER DETAILS
1.3 Gain/filter setting servo parameters group ([Pr. PB_ _ ])
[Pr. PB34_Gain switching - Vibration suppression control 1 -
Resonance frequency (VRF12B)]
Set the resonance frequency for vibration suppression control 1 for when the gain switching is enabled.
When the setting value of this servo parameter is less than "0.1", the setting value of [Pr. PB20 Vibration suppression control
1 - Resonance frequency] is applied.
This servo parameter is enabled in the following conditions:
• [Pr. PA08.0 Gain adjustment mode selection] is set to "3" (manual mode).
• [Pr. PB02.0 Vibration suppression control 1 - Tuning mode selection] is set to "2" (manual setting).
• "1" (control command from the controller) is selected in [Pr. PB26.0 Gain switching selection].
Switching gains during driving may cause a shock. Switch the gains after the servo motor has stopped.
[Pr. PB35_Gain switching - Vibration suppression control 1 -
Vibration frequency damping (VRF13B)]
Set the damping of the vibration frequency for vibration suppression control 1 for when the gain switching is enabled.
This servo parameter is enabled in the following conditions:
• [Pr. PA08.0 Gain adjustment mode selection] is set to "3" (manual mode).
• [Pr. PB02.0 Vibration suppression control 1 - Tuning mode selection] is set to "2" (manual setting).
• "1" (control command from the controller) is selected in [Pr. PB26.0 Gain switching selection].
Switching gains during driving may cause a shock. Switch the gains after the servo motor has stopped.
[Pr. PB36_Gain switching - Vibration suppression control 1 -
Resonance frequency damping (VRF14B)]
Set the damping of the resonance frequency for vibration suppression control 1 for when the gain switching is enabled.
This servo parameter is enabled in the following conditions:
• [Pr. PA08.0 Gain adjustment mode selection] is set to "3" (manual mode).
• [Pr. PB02.0 Vibration suppression control 1 - Tuning mode selection] is set to "2" (manual setting).
• "1" (control command from the controller) is selected in [Pr. PB26.0 Gain switching selection].
Switching gains during driving may cause a shock. Switch the gains after the servo motor has stopped.
Initial value
Setting range
Setting method
Ver.
0.0 [Hz]
0.0 to 300.0
Each axis
C4
Initial value
Setting range
Setting method
Ver.
0.00
0.00 to 0.30
Each axis
C4
Initial value
Setting range
Setting method
Ver.
0.00
0.00 to 0.30
Each axis
C4