14
1 SERVO PARAMETER DETAILS
1.2 Basic setting servo parameters group ([Pr. PA_ _ ])
[Pr. PA02.4_Simple converter selection]
When using the simple converter, set this servo parameter.
The simple converter and external regenerative option can be used together. When using an external regenerative option, set
the regenerative option to be used with [Pr. PA02.0-1].
When [Pr. PA02.0-1 Regenerative option selection] is set to "01" (FR-XC-(H)), setting this servo parameter to "1" (enabled)
triggers [AL. 037 Parameter error].
0: Simple converter is not used
1: MR-CM3K
[Pr. PA02.5_Excessive regeneration warning enabled/disabled selection]
When [Pr. PA02.4] is set to "0" (simple converter is not used), setting this servo parameter to "1" (disabled) triggers [AL. 037
Parameter error].
When the simple converter is used, whether to enable or disable the detection of [AL. 0E0.1 Excessive regeneration warning]
is selectable with this servo parameter.
0: Enabled
1: Disabled
Initial value
Setting range
Ver.
0h
Refer to the text
C4
Initial value
Setting range
Ver.
0h
Refer to the text
C4
Summary of Contents for MR-J5-B
Page 2: ......
Page 153: ...4 SERVO PARAMETER SETTING METHOD 4 2 Controller 151 4 MEMO ...
Page 157: ......