2 SYSTEM CONFIGURATION
2.3 System Configuration Specifications
53
2
Number of remote I/O points
When the master module of the network is used, calculate the number of remote I/O points connected on the network.
The maximum number of remote I/O points differs according to type of the network.
■
CC-Link IE Field Network Basic
Remote I/O points that are used in CC-Link IE Field Network Basic are calculated as "number of occupied stations
64
points".
The maximum number of remote I/O points differs depending on the CPU module and firmware version being used.
*1 Not calculated as remote I/O points. For details, refer to the following.
CC-Link IE Field Network Basic Reference Manual
■
CC-Link
The number of remote I/O points to be used in CC-Link is calculated as "number of remote I/O stations
32 points".
Even if using less than 32 remote I/O points, calculate as "number of remote I/O stations
32 points".
The maximum number of remote I/O points differs depending on the CPU module and firmware version being used.
Maximum number of the connected stations of the remote device station and the intelligent device station is
14 regardless of the number of remote I/O points.
For details, refer to the following.
MELSEC iQ-F FX5 User's Manual (CC-Link)
■
AnyWireASLINK
The number of I/O points set below is assigned to the remote I/O to be used with AnyWireASLINK.
• FX5-ASL-M: Set with the engineering tool parameters.
• FX3U-128ASL-M: Set with the rotary switch on the FX3U-128ASL-M main body.
For details, refer to the following.
MELSEC iQ-F FX5 User's Manual (AnyWireASLINK)
FX3U-128ASL-M User's Manual
The maximum number of remote I/O points differs depending on the CPU module and firmware version being used.
CPU module
Firmware version
Maximum number of remote I/O points
FX5S CPU module
FX5UJ CPU module
No restrictions
FX5U CPU module
FX5UC CPU module
1.110 or higher
1.100 or higher, but lower than 1.110
512 points maximum
Lower than 1.100
384 points maximum
CPU module
Firmware version
Maximum number of remote I/O points
FX5-CCL-MS (when master
station)
FX3U-16CCL-M
FX5UJ CPU module
No restrictions
192 points maximum
FX5U CPU module
FX5UC CPU module
1.100 or higher
448 points maximum
256 points maximum
Lower than 1.100
384 points maximum
256 points maximum
CPU module
Firmware version
Maximum number of remote I/O points
FX5-ASL-M
FX3U-128ASL-M
FX5UJ CPU module
No restrictions
216 points maximum
FX5U CPU module
FX5UC CPU module
1.100 or higher
448 points maximum
128 points maximum
Lower than 1.100
384 points maximum
128 points maximum
Summary of Contents for MELSEC iQ-F FX5UC Series
Page 2: ......
Page 142: ...140 8 CONNECTOR CONVERSION MODULE PERFORMANCE SPECIFICATIONS 8 2 External Dimensions MEMO ...
Page 144: ...142 9 SD MEMORY CARD PERFORMANCE SPECIFICATIONS 9 2 Formatting MEMO ...
Page 146: ...144 10 BATTERY PERFORMANCE SPECIFICATIONS 10 2 Battery Life MEMO ...
Page 277: ...I 275 MEMO ...
Page 281: ......