2 SYSTEM CONFIGURATION
2.3 System Configuration Specifications
45
2
Number of connected extension modules
A maximum of 12 extension modules can be connected on the right side of the CPU module.
The connector conversion modules are not included in the number of connected modules.
When powered input/output modules or extension power supply modules are used, a maximum of 16 extension modules can
be connected.
The extension power supply modules are not included in the number of connected modules.
*1 Maximum number of connectable intelligent function modules is eight.
*2 When the modules of extension cable type are connected after the extension power supply modules (extension connector type), the
connector conversion modules cannot be used.
■
Number of connected FX3 extension modules
A maximum of six FX3 extension modules can be connected on the right side of the bus conversion module.
When an FX3 extension power supply module is used, a maximum of eight FX3 extension modules can be connected.
...
11
1
2
12
Up to 12
*1
...
...
...
11
1
2
12
9
2
10
9
2
10
1
1
Up to 16
Up to 12
*1
Up to 10
*1
Powered
input/output module,
FX5 extension power
supply module
*2
Up to 10
*1
Powered
input/output module,
FX5 extension power
supply module
*2
...
...
5
1
2
6
Up to 6
Bus
conversion
module
...
...
7
1
2
8
Up to 8
FX3 extension
power supply
module
Bus
conversion
module
Summary of Contents for MELSEC iQ-F FX5UC Series
Page 2: ......
Page 142: ...140 8 CONNECTOR CONVERSION MODULE PERFORMANCE SPECIFICATIONS 8 2 External Dimensions MEMO ...
Page 144: ...142 9 SD MEMORY CARD PERFORMANCE SPECIFICATIONS 9 2 Formatting MEMO ...
Page 146: ...144 10 BATTERY PERFORMANCE SPECIFICATIONS 10 2 Battery Life MEMO ...
Page 277: ...I 275 MEMO ...
Page 281: ......