220
13 WIRING
13.7 Wiring Examples for Various Uses
Digital switch
When DSW instructions are used
Wiring examples for capturing values from a 4-digit digital switch to the data register D100 are given below.
For the instructions, refer to
MELSEC iQ-F FX5 Programming Manual (Instructions, Standard Functions/Function Blocks).
■
Program example
■
Wiring example
• Sink wiring
The example is the wiring for the input/output of the FX5U-32MT/ES.
The example is the wiring for the input/output of theFX5UC-32MT/D.
*1 The grounding resistance should be 100
or less.
DSW
SM400
X10
Y10
D100
K1
X10
X11
X12
X13
X15
X14
X16
X17
COM2 Y10
Y11
Y12
Y13
FX5U-32MT/ES
1
2
4
8
10
3
10
2
10
1
10
0
10
3
10
2
10
1
10
0
S/S
0V
24V
BCD digital switch
0.1A/50V diode required
Sink input
Transistor output (sink)
COM
X10
X11
X12
X13
X15
X14
X16
X17
COM0 Y10
Y11
Y12
Y13
FX5UC-32MT/D
1
2
4
8
10
3
10
2
10
1
10
0
10
3
10
2
10
1
10
0
COM0
*1
BCD digital switch
24VDC
Fuse
0.1A/50V diode required
Class-D
grounding
Sink input
Transistor output (sink)
Summary of Contents for MELSEC iQ-F FX5UC Series
Page 2: ......
Page 142: ...140 8 CONNECTOR CONVERSION MODULE PERFORMANCE SPECIFICATIONS 8 2 External Dimensions MEMO ...
Page 144: ...142 9 SD MEMORY CARD PERFORMANCE SPECIFICATIONS 9 2 Formatting MEMO ...
Page 146: ...144 10 BATTERY PERFORMANCE SPECIFICATIONS 10 2 Battery Life MEMO ...
Page 277: ...I 275 MEMO ...
Page 281: ......