12 INSTALLATION
12.1 Installation Positions
Layout in control panel
The programmable controller components can be laid out in one stage or in two stages (upper and lower).The connecting
procedures in each case are explained below.
Extension devices can be connected on the left and right sides of the CPU module of the programmable controller. (For the
FX5S CPU module, extension devices can be connected on the left of the CPU module located in the middle.)
Keep a space of at least 50mm between the module main body or other devices and structure.
Also, separate the programmable controller from high-voltage lines, high-voltage devices, and power devices when possible.
Failure to do so may cause fire, equipment failures or malfunctions.
When extension devices are intended to add, keep necessary spaces on the left and right sides.
Configuration in 1-stage layout
Configuration in 2-stage layout
For product dimensions, refer to the external dimensions diagram of each product.
FX5-16EX/ES
FX5-232ADP
FX5-16EYT/ES
≥
50mm
CPU module
FX5-40SSC-S
FX5-40SSC-S
• FX5-30EC
• FX5-65EC
FX5-16EX/ES
FX5-16EYT/ES
FX5-16EYT/ES
FX5-16EYT/ES
FX5-232ADP
≥
50mm
FX5-CNV-BC
FX5-16EX/ES
Other device
CPU module
Extended extension
cable
Powered
input/output
module
Other device
Other device
Summary of Contents for MELSEC iQ-F FX5UC Series
Page 2: ......
Page 142: ...140 8 CONNECTOR CONVERSION MODULE PERFORMANCE SPECIFICATIONS 8 2 External Dimensions MEMO ...
Page 144: ...142 9 SD MEMORY CARD PERFORMANCE SPECIFICATIONS 9 2 Formatting MEMO ...
Page 146: ...144 10 BATTERY PERFORMANCE SPECIFICATIONS 10 2 Battery Life MEMO ...
Page 277: ...I 275 MEMO ...
Page 281: ......