Number of I/O points (including the number of occupied I/O points)
The number of input/output points is the sum of the following numbers of the points.
• Number of input/output points on CPU module and I/O module
• Number of occupied input/output points of intelligent function modules, safety main modules, and bus conversion modules
■
Number of I/O points on CPU module and I/O modules
Count the total number of input/output points of the CPU module and I/O modules.
For the number of I/O points, count the total number of input points (X0 and more) and output points (Y0 and more) of the
CPU module and I/O modules.
For details on the number of I/O points by model, refer to the following.
• Example of number of I/O points
■
Number of occupied I/O points
Count the number of occupied input/output points of intelligent function modules, safety main modules, and bus conversion
modules.
The number of occupied I/O points per module is 8.
Extension power supply modules, connector conversion modules, expansion boards, and expansion adapters have no
occupied I/O points.
• Example of number of occupied I/O points
Module
Model
Number of
input
points
Number of
output
points
Number of
I/O points
Description
CPU module
FX5UJ-24MR/ES
10 points (16
points)
14 points (16
points)
24 points (32
points)
The number in brackets "()" is the number of
occupied points. When calculating the total number
of I/O points, the values in the brackets "( )" are
used. The number of I/O points is therefore 32.
Number of input points (16) + Number of output
points (16) = Number of I/O points (32)
FX5U-32MT/ES
16 points
16 points
32 points
The number of I/O points is 32.
Number of input points (16) + Number of output
points (16) = Number of I/O points (32)
Input module
FX5-16EX/ES
16 points
16 points
The number of I/O points is 16.
Output module
FX5-16EYT/ES
16 points
16 points
The number of I/O points is 16.
Module
Model
Number of occupied
I/O points
Description
Expansion board
FX5-232-BD
No occupied points
Expansion adapter
FX5-232ADP
No occupied points
Simple motion module
FX5-40SSC-S
8 points
Eight points are occupied because this module is an
intelligent function module.
Bus conversion module
FX5-CNV-BUS
8 points
Eight points are occupied because this module is a bus
conversion module.
Analog input
FX3U-4AD
8 points
Eight points are occupied because this module is an
intelligent function module.
Summary of Contents for MELSEC iQ-F FX5UC Series
Page 2: ......
Page 142: ...140 8 CONNECTOR CONVERSION MODULE PERFORMANCE SPECIFICATIONS 8 2 External Dimensions MEMO ...
Page 144: ...142 9 SD MEMORY CARD PERFORMANCE SPECIFICATIONS 9 2 Formatting MEMO ...
Page 146: ...144 10 BATTERY PERFORMANCE SPECIFICATIONS 10 2 Battery Life MEMO ...
Page 277: ...I 275 MEMO ...
Page 281: ......