166
13 WIRING
13.2 Preparation of Wiring Components
■
Installation
Place the terminal block at its predetermined position and tighten the terminal block mounting screws on the left and right
sides uniformly.
Note that there is no gap between the terminal block and mount position.
Precautions
Do not tighten the terminal block mounting screws with torque exceeding the specified range. Doing so may cause failures or
malfunctions.
European-type terminal block
Wire the European-type terminal block in accordance with the following specifications.
Suitable wiring
Precautions
Do not tighten terminal screws with torque beyond the specified range. Doing so may cause failures or malfunctions.
Product
Number of
wires
connected
per terminal
Wire size
Tightening torque
Solid wire, Stranded wire
Wire ferrule with insulation
sleeve
Built-in analog I/O terminal block
Terminal block for built-in RS-485
communications
One wire
0.2 to 0.5
(24 to 20 AWG)
0.2 to 0.5
(24 to 20 AWG)
0.22 to 0.25N
m
Two wires
0.2
(24 AWG)
Expansion board, communication
adapter
One wire
0.3 to 0.5
(22 to 20 AWG)
0.3 to 0.5
(22 to 20 AWG)
Two wires
0.3
(22 AWG)
Analog adapter
One wire
0.3 to 0.5
(22 to 20 AWG)
0.3 to 0.5
(22 to 20 AWG)
0.20 N
m
Two wires
0.3
(22 AWG)
Summary of Contents for MELSEC iQ-F FX5UC Series
Page 2: ......
Page 142: ...140 8 CONNECTOR CONVERSION MODULE PERFORMANCE SPECIFICATIONS 8 2 External Dimensions MEMO ...
Page 144: ...142 9 SD MEMORY CARD PERFORMANCE SPECIFICATIONS 9 2 Formatting MEMO ...
Page 146: ...144 10 BATTERY PERFORMANCE SPECIFICATIONS 10 2 Battery Life MEMO ...
Page 277: ...I 275 MEMO ...
Page 281: ......