966
FX
3G
/FX
3U
/FX
3UC
Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
B Instruction Execution Time
B-1 Basic Instruction Execution Time
*1.
M1536 to M3583, M8256 to M8511, S1024 to S4095
*2.
M1536 to M3583, M8000 to M8511
*3.
M3584 to M7679
Output instructions
OUT T D
3.55
3.32
T246 to T319
3.83
µ
s in execution in ON status
3.19
µ
s in execution in OFF status
OUT C K
2.68
3.02
2.35
2.89
C235 to C255
2.66
µ
s in execution in ON status
1.45
µ
s in execution in OFF status
OUT C D
3.04
3.25
2.72
3.1
C235 to C255
3.00
µ
s in execution in ON status
1.45
µ
s in execution in OFF status
SET Y,M
0.44
0.88
µ
s in 2-step instruction
*2
0.88
µ
s in 3-step instruction
*3
SET S
1.62 or 1.66 + 0.55n
0.78
n: Number of recombination
n=1.62 when there is no
recombination
RST Y,M
0.44
0.88
µ
s in 2-step instruction
*2
0.88
µ
s in 3-step instruction
*3
RST S
1.55
0.78
RST T
2.08
1.6
RST C
2.08
2.31
1.19
1.58
RST D
1.66
0.74
PLS Y,M
1.88
1.88
µ
s in M3584 to M7679
PLF Y,M
1.88
1.88
µ
s in M3584 to M7679
Master control instructions
MC
2.01
2.13
MCR
1.51
⎯
Other instruction
NOP
0.42
End instruction
END
292 + 2.5X + 3.75Y
⎯
Even if FEND and END are used
together, execution time of only
END is required.
X: Number of input points,
Y: Number of output points
Instruction
Execution time in ON status (
µ
s)
Execution time in OFF status (
µ
s)
Remarks
16-bit instruction
32-bit instruction
16-bit instruction
32-bit instruction