Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
38 Error Check Method and Error Code List
38.4 Error Code List and Action
31
FN
C
275-
FN
C
279
Da
ta
Transf
er 3
32
FN
C
280-
FN
C
289
H
igh Speed
Pr
ocessing 2
33
FN
C
29
0-F
N
C
299
Ext
ens
ion Fi
le
R
egi
ster
34
FN
C
300-
FN
C
305
FX
3U
-C
F-A
D
P
35
SFC•S
TL
Pr
ogr
am
m
ing
36
In
ter
rupt
Functi
on
37
Special D
evice
38
E
rro
r C
ode
A
Ve
rs
ion U
p
In
fo
rm
atio
n
B
Execution T
im
es
6112
Stops
operation
Changed settings for the built-in CC-Link/LT
special function block cannot be written to the
attached flash memory cassette.
Verify that the memory cassette is installed
correctly.
6113
Changed settings for the built-in CC-Link/LT
special function block cannot be written to the
attached write-protected flash memory cassette.
Set the protect switch to OFF.
6114
CC-Link/LT settings cannot be written to the built-in
CC-Link/LT special function block.
6115
A built-in CC-Link/LT special function block
EEPROM writing time-out error occurred, or the
built-in CC-Link/LT special function block
configuration could not be completed normally in
self CONFIG mode.
PLC/PP communication error (D8062)
Serial communication error 0 [M8062 (D8062)]
0000
⎯
No error
6201
Continues
operation
Parity, overrun or framing error
Confirm the cable connection between the
programming panel (PP)/programming device and
the PLC. This error may occur when a cable is
disconnected an reconnected during PLC
monitoring.
6202
Communication character error
6203
Communication data sum check error
6204
Data format error
6205
Command error
Serial communication error 1 [M8063 (D8063)]
0000
⎯
No error
6301
Continues
operation
Parity, overrun or framing error
• Inverter communication, computer link and
programming:
Ensure the communication parameters are
correctly set according to their applications.
• N:N network, parallel link, etc.:
Check programs according to applications.
• Remote maintenance:
Ensure modem power is ON and check the
settings of the AT commands.
• Wiring:
Check the communication cables for correct
wiring.
6302
Communication character error
6303
Communication data sum check error
6304
Communication data format error
6305
Command error
6306
Communication time-out detected
6307
Modem initialization error
6308
N:N network parameter error
6312
Parallel link character error
6313
Parallel link sum error
6314
Parallel link format error
6320
Inverter communication error
Parameter error [M8064(D8064)]
0000
⎯
No error
6401
Stops
operation
Program sum check error
STOP the PLC, and correctly set the parameters.
6402
Memory capacity setting error
6403
Latched device area setting error
6404
Comment area setting error
6405
File register area setting error
6406
Special unit (BFM) initial value setting, positioning
instruction setting sum check error
6407
Special unit (BFM) initial value setting, positioning
instruction setting error
6409
Other setting error
6411
Built-in CC-Link/LT special function block invalid
parameter settings (LT-2 dedicated area).
6412
Built-in CC-Link/LT special function block
parameter settings sum check error (special
function settings area).
6413
Built-in CC-Link/LT special function block
parameter settings sum check error (LT-2
dedicated area).
Error
code
PLC operation at
error occurrence
Contents of error
Action