37 Operation of Special Devices (M8000 -, D8000 -)
37.2 Supplement of Special Devices (M8000 - and D8000 -)
37.2.15 Individual operation for RUN/STOP input [M8035 to M8037]
When using external push button switches to control the PLC's RUN/STOP mode, operate the switches using
the following procedure.
The PLC enters RUN mode by one-shot input of the RUN switch, while one-shot input of the STOP switch
drives the STOP mode.
1. Program example
The figure on the left shows an example
for the FX
3U
PLC (sink input).
2. Setting method
1) Turn the built-in RUN/STOP switch to STOP.
2) Set up the RUN input switch, (X) (X000 is specified in the circuit diagram example above.)
Make the external RUN/STOP input valid by specifying an input between X000 and X017
*1
for the RUN
input signal.
*1. X000 to X007 in the FX
3U
-16M
, FX
3UC
-16M
and 14-point type FX
3G
PLCs, and X000 to X014
in 24-point type FX
3G
PLCs
a) Display the parameter setting in the programming tool
In GX Developer, double-click [Parameter] - [PC parameter] in the project tree to display the dialog
box.
Go to the "PLC system (1)" tab, and set "RUN terminal input."
b) Specify the input (X) number to switch from STOP mode to RUN mode.
X000
PLC
STOP
S/S
X001
M8000
Forced RUN mode
M8035
Forced RUN signal
M8036
Forced STOP signal
M8037
X001
Write the above program to the PLC.
RUN
0V
24V