Explanation of function and operation
These instructions are convenient in programming branched multi-output circuits.
1. MPS, MRD, and MPP instructions (stores the current result of the internal PLC operations,
reads the current result of the internal PLC operations, and pops (recalls and removes) the
currently stored result)
• Use MPS instruction to store the intermediate result of operation, and then drive the output Y002.
• Use MRD instruction to read the stored data, and then drive the output Y003.
MRD instruction can be programmed as many times as necessary.
• In the final output circuit, use MPP instruction instead of MRD instruction.
MPP instruction reads the stored data described above, and then resets it.
Error
MPS instruction can be used two or more times.
However, the difference between number of MPS instructions and the number of MPP instructions should be
11 or less, and should be 0 at the end.
X004
X005
Y002
Y004
X006
Y003
MPS
MRD
MPP
Y005
MRD
[2]
[1]
MPP
MRD
MPS
MPP
Stack
1
2
3
10
11
0018 LD
X004
0019
0020 AND X005
0021 OUT Y002
0022
0023 AND X006
0024 OUT Y003
0025
0026 OUT Y004
0027
0028 AND X007
0029 OUT Y005
0030 END
MPS
MRD
MRD
MPP
18
X007