Programming Manual - Basic & Applied Instruction Edition
33 Extension File Register Control – FNC290 to FNC299
33.1 FNC290 – LOADR / Load From ER
2) In FX
3G
PLCs
a) When a memory cassette is connected
The contents (current values) of extension file registers (ER) stored in a memory cassette (EEPROM)
having the same numbers with the extension registers specified by
to
+n-1 are read, and
transferred to the extension registers specified by
to
+n-1 stored in the PLC's built-in
RAM.
• Reading and transfer are executed in units of device. Up to 24000 devices can be read and
transferred.
b) When a memory cassette is not connected
In the program example below, the contents (current value) of extension file registers (ER) which are
stored in the EEPROM built in the PLC and have the same device numbers as extension registers
to
+n-1 are read, and transferred to extension registers (R) which are stored in the RAM
built in the PLC and have the device numbers
to
+n-1.
• Reading and transfer are executed in units of device. Up to 24000 devices can be read and
transferred.
S
S
S
S
FNC290
LOADRP
S
n
Command
input
E
E +1
E +2
E +3
E +n-2
E +n-1
+1
+2
+3
+n-2
+n-1
Read
(transfer)
Extension file registers (ER)
inside memory cassette
Extension registers (R)
inside built-in RAM
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
FNC290
LOADRP
S
n
Command
input
E
E +1
E +2
E +3
E +n-2
E +n-1
+1
+2
+3
+n-2
+n-1
Read
(transfer)
Extension file registers (ER)
inside built-in EEPROM
Extension registers (R)
inside built-in RAM
S
S
S
S
S
S
S
S
S
S
S
S