Programming Manual - Basic & Applied Instruction Edition
33 Extension File Register Control – FNC290 to FNC299
33.4 FNC293 – LOGR / Logging R and ER
31
FN
C
275-
FN
C
279
Da
ta
Transf
er 3
32
FN
C
280-
FN
C
289
H
igh Speed
Pr
ocessing 2
33
FN
C
29
0-F
N
C
299
Ext
ens
ion Fi
le
R
egi
ster
34
FN
C
300-
FN
C
305
FX
3U
-C
F-A
D
P
35
SFC•S
TL
Pr
ogr
am
m
ing
36
In
ter
rupt
Functi
on
37
Special D
evice
38
E
rro
r C
ode
A
Ve
rs
ion U
p
In
fo
rm
atio
n
B
Execution T
im
es
Cautions
1. LOGR instruction
LOGR instruction executes logging in each operation in the continuous operation type.
When logging should be executed only once by one input, use the pulse operation type.
2. Caution on using a memory cassette
Flash memory is adopted in a memory cassette. Make sure to initialize the data storage area in units of
sector before starting logging.
If LOGR instruction is executed without initializing the data storage area, an operation error (error code:
K6770) may be caused.
3. Allowable number of writes to the memory
Note the following cautions on access to extension file registers.
• Data can be written to the memory cassette (flash memory) up to 10,000 times.
Every time the INITR (FNC292), RWER (FNC294) or INITER (FNC295) instruction is executed, it is
counted as a write to the memory. Make sure not to exceed the allowable number of writes.
When a continuous operation type instruction is used, data is written to the memory in every operation
cycle of the PLC. For preventing this, make sure to use a pulse operation type instruction.
• Execution of the LOADR (FNC290), SAVER (FNC291) or LOGR (FNC293) instruction is not counted as a
write to the memory. However, it is necessary to initialize the writing target sector before executing the
SAVER (FNC291) or LOGR (FNC293) instruction.
Every time the INITR (FNC292)or INITER (FNC295) instruction is executed, it is counted as a write to the
memory. Make sure not to exceed the allowable number of writes.
n
FNC292
INITR
D
1
Logging data storage area initialization
command input
*1
*2
*1 Specify the same device as in LOGR instruction.
*2 Specify the same number as (n) in LOGR instruction.
D
1