37 Operation of Special Devices (M8000 -, D8000 -)
37.2 Supplement of Special Devices (M8000 - and D8000 -)
31
FN
C
275-
FN
C
279
Da
ta
Transf
er 3
32
FN
C
280-
FN
C
289
H
igh Speed
Pr
ocessing 2
33
FN
C
29
0-F
N
C
299
Ext
ens
ion Fi
le
R
egi
ster
34
FN
C
300-
FN
C
305
FX
3U
-C
F-A
D
P
35
SFC•S
TL
Pr
ogr
am
m
ing
36
In
ter
rupt
Functi
on
37
Special D
evice
38
E
rro
r C
ode
A
Ve
rs
ion U
p
In
fo
rm
atio
n
B
Execution T
im
es
37.2
Supplement of Special Devices (M8000 - and D8000 -)
This section explains how to use the provided special devices to activate built-in PLC functions for additional
program control.
37.2.1 RUN monitor and initial pulse [M8000 to M8003]
1. RUN monitor (M8000 and M8001)
The RUN monitor (M8000 and M8001) may be used to continually drive an output during PLC "normal
operation."
1) Example program
M8001 is always OFF while the PLC is in the RUN mode.
2) Flag operation timing
2. Initial pulse (M8002 and M8003)
The initial pulse M8002 & M8003 is turned to ON or OFF respectively during the 1st scan of the PLC program.
It can be utilized as an initial setting signal in a program for initializing the program, for writing a specified
value, or for another purpose.
1) Example program
M8003 turns OFF momentarily (for only 1 scan time) when the PLC enters the RUN mode.
2) Flag operation timing
M8000
RUN monitor (NO contact)
Always ON while the PLC
is in RUN mode.
"Normal operation"
Y000
Output to be always driven
RUN input
RUN
STOP
RUN
M8000
RUN monitor (NO contact)
ON
ON
M8001
RUN monitor (NC contact)
ON
M8002
Initial pulse (NO contact) ON
ON
1 scan time
M8003
Initial pulse (NC contact)
ON
ON
M8002
Initial pulse (NO contact)
FNC40
ZRST
D200
D299
The latched (battery backed) type data registers D200
to D299 are cleared.
RUN input
RUN
STOP
RUN
M8000
RUN monitor (NO contact)
ON
ON
M8001
RUN monitor (NC contact)
ON
M8002
Initial pulse (NO contact) ON
ON
1 scan time
M8003
Initial pulse (NC contact)
ON
ON