VII
Control ]
- 92 -
HWE1312A
GB
Control at Initial Start-up
-8- Peak-demand control
General idea about demand control in the system with a combination of a heat pump and a combustion-type hot water boiler.
→During peak-demand hours, the operation of the air conditioning units is given higher priority than that of the heat pump units.
1.Individual system
The peak-demand control function is a function that restricts the maximum capacity of the units. The maximum operation
capacities of the units are restricted to specific levels relative to the maximum capacity of the units (= the compressors are
operating at the maximum rotation speed (100 Hz on the unit described in this manual)) being set as 100%.
100%
(100Hz)
The compressor will operate at the maximum rotation speed of 80 Hz.
2.Peak-demand control in a multiple system
The peak-demand control function is a function that restricts the maximum capacity of the units. The maximum operation
capacities of the units are restricted to specific levels relative to the maximum capacity of all units (= the compressors are
operating at the maximum rotation speed (100 Hz on the unit described in this manual)) being set as 100%.
Standard operation
The units are designed to operate in the patterns as shown below to optimize operation efficiency.
a. Maximum capacity setting (D%) ≥ 70% → All units will be operated at D Hz.
320
%
No. 1 unit
No. 2 unit
No. 3 unit
No. 4 unit
80%
100%
400
%
<100
%
>
Entire system
No. 1 unit
No. 2 unit
No. 3 unit
No. 4 unit
No. 1 unit
No. 2 unit
No. 3 unit
No. 4 unit
Entire system
Distribution of capacity
The maximum capacity of each unit is set as 100%.
(The figures in the angle brackets indicate the total
capacity in the entire system.)
b. Maximum capacity setting D% < 70% →
The number of units "N" and the capacity at which the units operate ”α" will be
determined so that either the condition (1) or (2) below is met.
1 ) D × M = 70% × (N-1) + α × 1 (40 % ≤ α < 70 % )
(N-1) units will be operated at 70 Hz, and one unit will be operated at α Hz.
200%
400
%
<100%>
400
%
<100%>
400
%
<100%>
70%
70%
60 %
0 %
2 ) D × M = α× N
70% ≤ α, The α value will be set to a value as close to 70 Hz as possible.
N units will be operated at α Hz.
200%
70%
70%
70 %
α :30% < 40 %
Re-distribution of capacity
Re-distribution of capacity
Re-distribution of capacity
Re-distribution
of capacity
Nomenclature
note. During the heating season, the unit will
not be operated at 100 Hz to save
energy consumption in the first place,
so the unit's performance may not be
affected even if the maximum capacity
setting is changed.
D %
Maximum capacity setting:
The capacity of the system when all units are operated at 100 Hz will be set as 100%.
M
Total number of units
N
No. of units in operation (calculated value)
α % ( α Hz)
Operating capacity (calculated value)
80%
80%
80 %
0%
240%
80%
Preset value
<80
%
>
Preset value
<50%>
Preset value
<50%>
Preset value
<60%>
Preset value
Summary of Contents for CRHV-P600YA-HPB
Page 1: ......
Page 7: ...CONTENTS HWE1312A GB ...
Page 9: ... 2 HWE1312A GB ...
Page 19: ... 12 HWE1312A GB ...
Page 41: ... II Restrictions 34 HWE1312A GB ...
Page 43: ... 36 HWE1312A GB ...
Page 51: ... III Unit Components 44 HWE1312A GB ...
Page 52: ... 45 HWE1312A GB IV Remote Controller 1 Using the Remote Controller 47 2 Function Settings 52 ...
Page 53: ... 46 HWE1312A GB ...
Page 61: ... IV Remote Controller 54 HWE1312A GB ...
Page 62: ... 55 HWE1312A GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 57 ...
Page 63: ... 56 HWE1312A GB ...
Page 67: ... V Electrical Wiring Diagram 60 HWE1312A GB ...
Page 69: ... 62 HWE1312A GB ...
Page 73: ... VI Refrigerant Circuit 66 HWE1312A GB ...
Page 75: ... 68 HWE1312A GB ...
Page 107: ... VII Control 100 HWE1312A GB ...
Page 109: ... 102 HWE1312A GB ...
Page 117: ... 110 HWE1312A GB ...
Page 165: ... IX Troubleshooting 158 HWE1312A GB ...
Page 166: ... 159 HWE1312A GB X Attachments 1 R410A saturation temperature table 161 ...
Page 167: ... 160 HWE1312A GB ...
Page 170: ......