VII
Control ]
- 96 -
HWE1312A
GB
2. Normal
Thermo-ON/OFF operations
DIFF1 = 2 ºC (Initial setting): “1015” Digitally set value
DIFF2 = 2 ºC (Initial setting): “1016” Digitally set value
Tmax=67 ºC
1) Thermo-ON/OFF temperature conditions
Intlet-temperature-based water temperature control in an individual system (with the external water temperature sen-
sor setting being set to ON and the Inlet-/outlet-based control option being set to inlet)
Outlet-temperature-based water temperature control in an individual system (with the external water temperature
sensor setting being set to ON and the Inlet-/outlet-based control option being set to outlet)
Single/Multiple
system
sensor
Thermo-ON
conditions
Thermo-ON
conditions
Thermo-OFF conditions
Individual
system
Built-in
thermistor
Inlet-water-temper-
ature-based control
Inlet water temperatures is low-
er than the "Inlet temperature
at Thermo-OFF - DIFF2ºC"
and the system is not in the
short-cycling protection mode.
Inlet water temperatures are
greater than the "set tempera-
ture + DIFF2 value (ºC)" AND
at least 60 seconds have
passed since the last Thermo-
ON.
Outlet-water-tem-
perature-based
control
Inlet temperatures are below
the "Inlet temperature at Ther-
mo-OFF - DIFF2ºC"AND the
average outlet temperature is
at or below "Preset tempera-
ture + DIFF2ºC" AND the sys-
tem is not in the short-cycling
protection mode.
Average outlet water tempera-
ture is greater than the "set
tempe DIFF2 value
(ºC)" AND at least 60 seconds
have passed since the last
Thermo-ON.
Representative
water
temperature
Water temperature
control based on the
external water tem-
perature reading
Inlet water temperatures is low-
er than the "Inlet temperature
at Thermo-OFF - DIFF2ºC"
External water temperature
sensor reading is greater than
the "set temperature * DIFF2
value (ºC)" AND at least 60
seconds have passed since
the last Thermo-ON.
Multiple
system
Representative
water
temperature
Water temperature
control based on the
external water tem-
perature reading
External water temperature
thermistor reading < Set tem-
perature - DIFF 2 value (ºC)
AND the anti-short-cycling pro-
tection function is not been trig-
gered.
The number of units to run an
optimal operation will be deter-
mined by the main unit.
(The unit with the least amount
of cumulative operation hours
will go into operation first.)
External water temperature
sensor reading is greater than
the "set temperature * DIFF2/2
value (ºC)" AND at least 60
seconds have passed since
the last Thermo-ON.
The number of units to run an
optimal operation will be
determined by the main unit.
(The unit with the least amount
of cumulative operation hours
will go into operation first.)
When the water temperature is controlled based on the inlet
temperature, compressor frequency will be controlled as
described in section -3- "Compressor frequency" (page 88).
(Automatic operation according to the preset temperature)
When the water temperature is controlled based on the
external water temperature sensor reading (outlet water
temperature), compressor frequency will be controlled in the
way that the target water temperature will be maintained. If
there is a sudden increase in water temperature and the unit
did not stop at the preset temperature, the unit will stop when
the temperature that equals "the preset tempe the
value set for DIFF2" is reached.
DIFF2°C
Thermo-OFF temperature
Preset water temperature
Inlet water
temperature changes
DIFF2°C
Outlet water temperature
changes 1
Outlet water temperature
changes-2
The unit will restart when the inlet water temperature
drops from the inlet temperature at the time of
Thermo-OFF by more than the value set for DIFF2.
Thermo-OFF temperature
Preset water
temperature
Summary of Contents for CRHV-P600YA-HPB
Page 1: ......
Page 7: ...CONTENTS HWE1312A GB ...
Page 9: ... 2 HWE1312A GB ...
Page 19: ... 12 HWE1312A GB ...
Page 41: ... II Restrictions 34 HWE1312A GB ...
Page 43: ... 36 HWE1312A GB ...
Page 51: ... III Unit Components 44 HWE1312A GB ...
Page 52: ... 45 HWE1312A GB IV Remote Controller 1 Using the Remote Controller 47 2 Function Settings 52 ...
Page 53: ... 46 HWE1312A GB ...
Page 61: ... IV Remote Controller 54 HWE1312A GB ...
Page 62: ... 55 HWE1312A GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 57 ...
Page 63: ... 56 HWE1312A GB ...
Page 67: ... V Electrical Wiring Diagram 60 HWE1312A GB ...
Page 69: ... 62 HWE1312A GB ...
Page 73: ... VI Refrigerant Circuit 66 HWE1312A GB ...
Page 75: ... 68 HWE1312A GB ...
Page 107: ... VII Control 100 HWE1312A GB ...
Page 109: ... 102 HWE1312A GB ...
Page 117: ... 110 HWE1312A GB ...
Page 165: ... IX Troubleshooting 158 HWE1312A GB ...
Page 166: ... 159 HWE1312A GB X Attachments 1 R410A saturation temperature table 161 ...
Page 167: ... 160 HWE1312A GB ...
Page 170: ......