I
Read Before Servicing ]
- 8 -
HWE1312A
GB
[6] Refrigerant Charging
1. Reasons
R410A is a mixture of 2 refrigerants, each with a different evaporation temperature. Therefore, if the equipment is charged
with R410A gas, then the refrigerant whose evaporation temperature is closest to the outside temperature is charged frist
while the rest of refrigerants remain in the cylinder.
2. Notes
When using a cylinder with a siphon, refrigerant is charged in the liquid state without the need for turning it upside down. Check
the type of the cylinder on the label before use.
[7] Remedies to be taken in case of a Refrigerant Leak
If the refrigerant leaks out, all of the remaining refrigerant must be replaced with a new charge to maintain the proper composition
of the refrigerant. Repair the leak, and then charge the system with the specified amount of refrigerant (4.5 kg). (Charge refrigerant
in the liquid state.)
Refer to "IX [4] Refrigerant Leak."(page 141)
Cylinder with a siphon
Cylinder color R410A is Pink.
Refrigerant charging in the liquid state
Charge refrigerant through the
check joint on the high-pressure side.
Charging refrigerant through the
check joint on the low-pressure side
will create reverse pressure,
resulting in compressor malfunctions.
Cylin-
der
liquid
Valve
Valve
liquid
Cylin-
der
Cylinder without a siphon
Summary of Contents for CRHV-P600YA-HPB
Page 1: ......
Page 7: ...CONTENTS HWE1312A GB ...
Page 9: ... 2 HWE1312A GB ...
Page 19: ... 12 HWE1312A GB ...
Page 41: ... II Restrictions 34 HWE1312A GB ...
Page 43: ... 36 HWE1312A GB ...
Page 51: ... III Unit Components 44 HWE1312A GB ...
Page 52: ... 45 HWE1312A GB IV Remote Controller 1 Using the Remote Controller 47 2 Function Settings 52 ...
Page 53: ... 46 HWE1312A GB ...
Page 61: ... IV Remote Controller 54 HWE1312A GB ...
Page 62: ... 55 HWE1312A GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 57 ...
Page 63: ... 56 HWE1312A GB ...
Page 67: ... V Electrical Wiring Diagram 60 HWE1312A GB ...
Page 69: ... 62 HWE1312A GB ...
Page 73: ... VI Refrigerant Circuit 66 HWE1312A GB ...
Page 75: ... 68 HWE1312A GB ...
Page 107: ... VII Control 100 HWE1312A GB ...
Page 109: ... 102 HWE1312A GB ...
Page 117: ... 110 HWE1312A GB ...
Page 165: ... IX Troubleshooting 158 HWE1312A GB ...
Page 166: ... 159 HWE1312A GB X Attachments 1 R410A saturation temperature table 161 ...
Page 167: ... 160 HWE1312A GB ...
Page 170: ......