<MAIN> high-pressure check joint
<MAIN> low-pressure check joint
<SUB> low-pressure check joint
<SUB> high-pressure check joint
1. Perform evacuation with a vacuum pump from the
high-pressure check joints.
(Evacuating the system through the low-pressure check joint
will cause the oil in the refrigerant system to be discharged,
resulting in compressor malfunction.)
2. While evacuation is being performed, assemble the unit by
performing the procedure in reverse in the order of 6→5→4→
3.
3. Perform refrigerant charging from the high-pressure check
joints.
(Be sure to perform refrigerant charging from the
high-pressure check joints so that a back pressure is not
applied to the compressor.)
4. Attach the cover of the control box and the service panels to
complete the procedure.
Summary of Contents for CRHV-P600YA-HPB
Page 1: ......
Page 7: ...CONTENTS HWE1312A GB ...
Page 9: ... 2 HWE1312A GB ...
Page 19: ... 12 HWE1312A GB ...
Page 41: ... II Restrictions 34 HWE1312A GB ...
Page 43: ... 36 HWE1312A GB ...
Page 51: ... III Unit Components 44 HWE1312A GB ...
Page 52: ... 45 HWE1312A GB IV Remote Controller 1 Using the Remote Controller 47 2 Function Settings 52 ...
Page 53: ... 46 HWE1312A GB ...
Page 61: ... IV Remote Controller 54 HWE1312A GB ...
Page 62: ... 55 HWE1312A GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 57 ...
Page 63: ... 56 HWE1312A GB ...
Page 67: ... V Electrical Wiring Diagram 60 HWE1312A GB ...
Page 69: ... 62 HWE1312A GB ...
Page 73: ... VI Refrigerant Circuit 66 HWE1312A GB ...
Page 75: ... 68 HWE1312A GB ...
Page 107: ... VII Control 100 HWE1312A GB ...
Page 109: ... 102 HWE1312A GB ...
Page 117: ... 110 HWE1312A GB ...
Page 165: ... IX Troubleshooting 158 HWE1312A GB ...
Page 166: ... 159 HWE1312A GB X Attachments 1 R410A saturation temperature table 161 ...
Page 167: ... 160 HWE1312A GB ...
Page 170: ......