GB
-5- LEV in the main circuit
Operating range of the LEV
The opening range of the LEV is between 100 and 1400 (fully open).
LEV operation speed
Open 133 plus/sec
Close 200 plus/sec
At startup
For one minute and thirty seconds after startup, the valve will be fixed to the Initial Setting.
During operation
Ninety or more seconds after startup, the LEV opening will be controlled every 30 seconds according to the changes in com-
pressor frequency, pressure, and temperature.
The LEV will be controlled to keep the suction SH in 5K.
If the heat source outlet temperature reaches 16ºC or above, the MOP function will be triggered to keep the low pressure from
rising too high.
(The LEV opening will be decreased to keep the low pressure at or below 1.2 MPa.)
When the heat source inlet temperature is high and the hot water temperature is low (water temperature below 35ºC), the
function to keep the low pressure from rising too high will trip.
(The LEV opening will be decreased so that the compression ratio of 1.5 or above will be maintained.)
Refrigerant Recovery Control
-6- Operation during power failure
Duration of power failure 20 ms or shorter
20 ~ 200ms
200 ms or longer
Detection of power failure
Undetectable
Instantaneous power
failure
Detection of power failure
Operation during power failure
Normal
operation
During an instanta-
neous power failure,
the unit will be con-
trolled according to
the input status of
the circuit board im-
mediately before the
instantaneous power
failure.
All outputs will be turned off immedi-
ately after power failure.
Operation
after power is
restored
Automatic restoration
after power failure is set
to "Enabled" (SW3-2 is
set to ON.)
Normal
operation
The circuit board will
start receiving input.
The unit will be controlled according to
the input status of the circuit board im-
mediately before the power failure, ex-
cept that the input status of the dry
contact after the power is restored will
override the one before the power fail-
ure. For three minutes after the power
is restored, the unit will not operate.
Automatic restoration
after power failure is set
to "Disabled" (SW3-2 is
set to OFF.)
The unit will stop, displaying the error
code for power failure.
The error will be cleared when the op-
eration command signal is off.
Summary of Contents for CRHV-P600YA-HPB
Page 1: ......
Page 7: ...CONTENTS HWE1312A GB ...
Page 9: ... 2 HWE1312A GB ...
Page 19: ... 12 HWE1312A GB ...
Page 41: ... II Restrictions 34 HWE1312A GB ...
Page 43: ... 36 HWE1312A GB ...
Page 51: ... III Unit Components 44 HWE1312A GB ...
Page 52: ... 45 HWE1312A GB IV Remote Controller 1 Using the Remote Controller 47 2 Function Settings 52 ...
Page 53: ... 46 HWE1312A GB ...
Page 61: ... IV Remote Controller 54 HWE1312A GB ...
Page 62: ... 55 HWE1312A GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 57 ...
Page 63: ... 56 HWE1312A GB ...
Page 67: ... V Electrical Wiring Diagram 60 HWE1312A GB ...
Page 69: ... 62 HWE1312A GB ...
Page 73: ... VI Refrigerant Circuit 66 HWE1312A GB ...
Page 75: ... 68 HWE1312A GB ...
Page 107: ... VII Control 100 HWE1312A GB ...
Page 109: ... 102 HWE1312A GB ...
Page 117: ... 110 HWE1312A GB ...
Page 165: ... IX Troubleshooting 158 HWE1312A GB ...
Page 166: ... 159 HWE1312A GB X Attachments 1 R410A saturation temperature table 161 ...
Page 167: ... 160 HWE1312A GB ...
Page 170: ......