[6] Configuring the Settings
1
2
3
4
<1> Making the settings
Use the LED display and the three push switches (SWP1 (↑), SWP2 (↓), and SWP3 (Enter)) to change the current
settings on the circuit board and to monitor various monitored values.
(1) Setting procedures
Take the following steps to set the push switches SWP1 through SWP3. These switches must be set after the dip
switches SW2 and SW3 have been set.
The settings must be set only by a qualified personnel.
Normally an item code appears on the display.
(The figure at left shows the case where item code 1 is displayed.) Press SWP3
(Enter) to advance the item code.
↓
Press SWP3 (Enter) until the item code appears that corresponds to the item to change or
monitor its value.
The left figure shows a display example (Code 13 Built-in thermistor temperature
setting 2).
↓
Press either SWP1 (↑) or SWP2 (↓) to display the value that corresponds to the
selected item.
The current setting value will blink.
↓
The left figure shows that the current setting value is "60.0."
To decrease this value to 58.0, for example, press SWP2 (↓).
Press SWP1 (↑) to increase the value.
<To change the settings>
When the desired value is displayed (58.0 in the example at left), press SWP3 (Enter).
↓
The displayed value will stop blinking and stay lit.
A lit LED indicates that the new setting has been saved.
*Pressing SWP1 (↑) or SWP2 (↓) will change the blinking setting value, but the
change will not be saved until SWP3 (Enter) is pressed.
If SWP3 is not pressed within one minute, the change will not be saved and the
display will return to the item code display mode.
Press and hold SWP1 (↑) or SWP2 (↓) for one second or longer to fast forward
through the numbers.
<To view the monitored data>
Press SWP3 (Enter) while the LED display is blinking (see step 3 above) to stop the
blinking.
*The values of the items that can only be monitored will not change when SWP1 (↑)
or SWP2 (↓) is pressed.
The display will stop blinking and stay lit after a minute, and the display will
automatically return to the item code display regardless of the type of values
displayed.
To change the values of other items, repeat the steps from step 2 above.
SWP1
SWP3
Enter
SWP2
SWP1
SWP3
Enter
SWP2
SWP1
SWP3
Enter
SWP2
SWP1
SWP3
Enter
SWP2
Summary of Contents for CRHV-P600YA-HPB
Page 1: ......
Page 7: ...CONTENTS HWE1312A GB ...
Page 9: ... 2 HWE1312A GB ...
Page 19: ... 12 HWE1312A GB ...
Page 41: ... II Restrictions 34 HWE1312A GB ...
Page 43: ... 36 HWE1312A GB ...
Page 51: ... III Unit Components 44 HWE1312A GB ...
Page 52: ... 45 HWE1312A GB IV Remote Controller 1 Using the Remote Controller 47 2 Function Settings 52 ...
Page 53: ... 46 HWE1312A GB ...
Page 61: ... IV Remote Controller 54 HWE1312A GB ...
Page 62: ... 55 HWE1312A GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 57 ...
Page 63: ... 56 HWE1312A GB ...
Page 67: ... V Electrical Wiring Diagram 60 HWE1312A GB ...
Page 69: ... 62 HWE1312A GB ...
Page 73: ... VI Refrigerant Circuit 66 HWE1312A GB ...
Page 75: ... 68 HWE1312A GB ...
Page 107: ... VII Control 100 HWE1312A GB ...
Page 109: ... 102 HWE1312A GB ...
Page 117: ... 110 HWE1312A GB ...
Page 165: ... IX Troubleshooting 158 HWE1312A GB ...
Page 166: ... 159 HWE1312A GB X Attachments 1 R410A saturation temperature table 161 ...
Page 167: ... 160 HWE1312A GB ...
Page 170: ......