[
IX
Troubleshooting ]
- 119 -
HWE1312A
GB
[2] Troubleshooting
Troubleshooting according to the remote controller malfunction or the external input error
Both for MA remote controller and ME remote controller
1. If a problem occurs, please check the following. If a protection device has tripped and brought the unit to stop (when an error
code is blinking on the LED), resolve the cause of the error before resuming operation.
Resuming operation without removing the causes of an error may damage the unit and its components.
Problem
Check item
Cause
Solution
The unit does not
operate.
The fuse in the control
box is not blown.
The power lamp on the
circuit board is not lit.
The main power is not turned on.
Switch on the power.
The power lamp on the
circuit board is lit.
The pump interlock circuit is not con-
nected.
Connect the pump interlock circuit wiring to
the system.
The flow switch wiring is not connect-
ed.
Connect the flow switch wiring to the sys-
tem.
The fuse in the control
box is blown.
Measure the circuit
resistance and the
earth resistance.
Short-circuited circuit or ground fault
Resolve the cause, and replace the fuse.
The compressor does
not operate.
Protection devices
have not tripped.
INV board problem
Repair or replace the INV board.
Noise filter board problem
Repair or replace the noise filter board.
High-pressure cutout
switch has tripped.
1302
Abnormal
high
pressure
Dirty condenser
(scaling formation)
Clean the condenser.
Air in the refrigerant circuit
Vacuum the refrigerant circuit, and charge
it with refrigerant.
Water flow shortage
Secure enough water flow rate.
The discharge
temperature thermistor
has tripped.
1102
LEV fault in the main circuit
Replace the LEV in the main circuit.
Injection LEV fault
Replace the injection LEV.
Injection solenoid valve fault
Replace the solenoid valve.
Refrigerant gas leakage
Leakage test
Refrigerant undercharge
Repair the cause of refrigerant shortage,
evacuate the system, and charge the refrig-
erant circuit with refrigerant.
A thermistor error was
detected.
5101~5120
Broken or short-circuited thermistor
wiring
Check the thermistor wiring for broken con-
nections or short circuit.
Replace the thermistor.
Overcurrent passed
through the compres-
sor.
4250
Compressor motor
Replace the compressor.
Overload operation
Check the operation patterns.
Seized compressor shaft
Replace the compressor.
The pump interlock has
tripped.
The pump interlock circuit is not con-
nected.
Connect the pump interlock wiring.
The water pump is not operating.
Operate the pump.
Problem with the solenoid contactor for
the pump
Replace the solenoid contactor.
The flow switch has
tripped.
The flow switch wiring is not connect-
ed.
Connect the flow switch wiring to the sys-
tem.
Water flow shortage
Increase the water flow rate.
Flow switch contact failure
Polish the contact point.
Automatic Start/Stop
thermistor has tripped.
The water temperature has reached
above the preset temperature.
Normal
The motor whines, but
will not turn.
Contact failure at a connector terminal
Polish the contact point.
Loose wire connection
Tighten the wire connection.
Seized compressor or fan bearing
Disassemble the compressor or the fan,
and repair as necessary.
High-pressure is too high.
Check the operation patterns.
A momentary overcur-
rent was detected.
Burned, short-circuited, or ground
faulted motor
Replace the compressor, and clean the re-
frigerant circuit.
Summary of Contents for CRHV-P600YA-HPB
Page 1: ......
Page 7: ...CONTENTS HWE1312A GB ...
Page 9: ... 2 HWE1312A GB ...
Page 19: ... 12 HWE1312A GB ...
Page 41: ... II Restrictions 34 HWE1312A GB ...
Page 43: ... 36 HWE1312A GB ...
Page 51: ... III Unit Components 44 HWE1312A GB ...
Page 52: ... 45 HWE1312A GB IV Remote Controller 1 Using the Remote Controller 47 2 Function Settings 52 ...
Page 53: ... 46 HWE1312A GB ...
Page 61: ... IV Remote Controller 54 HWE1312A GB ...
Page 62: ... 55 HWE1312A GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 57 ...
Page 63: ... 56 HWE1312A GB ...
Page 67: ... V Electrical Wiring Diagram 60 HWE1312A GB ...
Page 69: ... 62 HWE1312A GB ...
Page 73: ... VI Refrigerant Circuit 66 HWE1312A GB ...
Page 75: ... 68 HWE1312A GB ...
Page 107: ... VII Control 100 HWE1312A GB ...
Page 109: ... 102 HWE1312A GB ...
Page 117: ... 110 HWE1312A GB ...
Page 165: ... IX Troubleshooting 158 HWE1312A GB ...
Page 166: ... 159 HWE1312A GB X Attachments 1 R410A saturation temperature table 161 ...
Page 167: ... 160 HWE1312A GB ...
Page 170: ......