II
Restrictions ]
- 23 -
HWE1312A
GB
4. Perform an initial setup. (MAIN circuit side)
(1) Set the rotary switch SWU3 (labeled A in the figure at right) to "F."
[EEEE] will appear in LED1 (labeled B in the figure at right). *1
(2) Press and hold the push switch (SWP3) (labeled C in the figure at right)
for one second or longer.
• While the system is starting up [9999] will appear on LED1 (labeled B
in the figure at right).
• When start-up is complete, a control property [0002] will appear.
• Then five seconds later [FFFF] will appear.
(3) Set the rotary switch SWU3 (labeled A in the figure at right) back to "0."
The start-up process is complete, and the settings for such items as
clock, peak-demand control, schedule, and thermistor settings can now
be made.
*1 If the start-up process has already been completed, [FFFF] (instead of [EEEE]) will appear when the rotary switch
SWU3 is set to "F."
(3) System configuration procedures : Multiple system
1. Set the dip switches and rotary switches.
(Switches on the MAIN circuit on the main unit* AND the MAIN and SUB circuits on all sub units)
System configuration diagram
Setting the switches on the main unit
MAIN circuit
(1) Set the dip switch SW2-8 to ON. (an external
water temperature sensor) (labeled A in the
figure at right)
(2) Set the dip switch SW2-9 to ON. (multiple unit
control)(labeled A in the figure at right)
SUB circuit
Nothing needs to be changed.
Refer to "Dip switch settings table" (page 69) for
further details.
Make sure the address of the MAIN circuit on the main unit is set to "1" (labeled B in the figure above) and that the
address of the SUB circuit on the main unit is set to "51" (labeled C in the figure above).
The address of each SUB circuit should equal the sum of the MAIN circuit address on the same unit and 50.
A
B
C
Unit (MAIN circuit)
10’s digit (0) 1’s digit (1)
(0)(0)
External
water
temperature
sensor
Field-supplied dry
contact switch/relay
or remote controller
(PAR-W21MAA)
SW2-8: ON
SW2-9: ON
Address: 1
Address: 51
SW2-9: ON
Address: 2
SW2-9: ON
Address: 1 + n
SW2-6: OFF
Address: 52
SW2-6: OFF
Address: 50 + n
Inter-unit wiring
(M-NET line)
* The main unit is the unit to which an external water temperature sensor is connected.
Main unit
Sub unit
"n"th unit
Sub unit
MAIN
PCB
SUB
PCB
MAIN
PCB
SUB
PCB
MAIN
PCB
SUB
PCB
A
B
C
Main unit (MAIN circuit)
Main unit (SUB circuit)
10’s digit (0) 1’s digit (1)
(0)
10’s digit (5) 1’s digit (1)
(0)
Summary of Contents for CRHV-P600YA-HPB
Page 1: ......
Page 7: ...CONTENTS HWE1312A GB ...
Page 9: ... 2 HWE1312A GB ...
Page 19: ... 12 HWE1312A GB ...
Page 41: ... II Restrictions 34 HWE1312A GB ...
Page 43: ... 36 HWE1312A GB ...
Page 51: ... III Unit Components 44 HWE1312A GB ...
Page 52: ... 45 HWE1312A GB IV Remote Controller 1 Using the Remote Controller 47 2 Function Settings 52 ...
Page 53: ... 46 HWE1312A GB ...
Page 61: ... IV Remote Controller 54 HWE1312A GB ...
Page 62: ... 55 HWE1312A GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 57 ...
Page 63: ... 56 HWE1312A GB ...
Page 67: ... V Electrical Wiring Diagram 60 HWE1312A GB ...
Page 69: ... 62 HWE1312A GB ...
Page 73: ... VI Refrigerant Circuit 66 HWE1312A GB ...
Page 75: ... 68 HWE1312A GB ...
Page 107: ... VII Control 100 HWE1312A GB ...
Page 109: ... 102 HWE1312A GB ...
Page 117: ... 110 HWE1312A GB ...
Page 165: ... IX Troubleshooting 158 HWE1312A GB ...
Page 166: ... 159 HWE1312A GB X Attachments 1 R410A saturation temperature table 161 ...
Page 167: ... 160 HWE1312A GB ...
Page 170: ......