- 83 -
HWE1312A
GB
(8) Setting the water temperature using analog signal input
• When dip switch SW2-7 is set to ON (Enable external input) and item code 1051 is set to "0", the target water
temperature varies with the preset temperatures A and B and the type of analog input signal.
• When the water temperature setting input signal type is set to 0 (4-20 mA)
• External analog input signal of 4 mA: Preset temp. A (Item code 11)
• External analog input signal of 20 mA: Preset temp. B (Item code 13)
• External analog input signal of between 6 and 18 mA: the preset temperature will be linearly interpolated.
• When the water temperature setting input signal type is set to 1 (0-10 V)
• External analog input signal of 0 V: Preset temp. A (Item code 11)
• External analog input signal of 10 V: Preset temp. B (Item code 13)
• External analog input signal of between 1 and 9 V: the preset temperature will be linearly interpolated.
• When the water temperature setting input signal type is set to 2 (1-5 V)
• External analog input signal of 1 V: Preset temp. A (Item code 11)
• External analog input signal of 5 V: Preset temp. B (Item code 13)
• External analog input signal of between 1.5 and 4.5 V: the preset temperature will be linearly interpolated.
• When the water temperature setting input signal type is set to 3 (2-10 V)
• External analog input signal of 2 V: Preset temp. A (Item code 11)
• External analog input signal of 10 V: Preset temp. B (Item code 13)
• External analog input signal of between 3 and 9 V: the preset temperature will be linearly interpolated.
Preset temp B
Preset temp A
6 mA
Input current
18 mA
4 mA
20 mA
Preset temp B
Preset temp A
0 V
Input voltage
9 V
1 V
10 V
Preset temp B
Preset temp A
1 .5V
Input voltage
4.5 V
1 V
5 V
Preset temp B
Preset temp A
3 V
Input voltage
9 V
2 V
10 V
*Due to the resistance of the wire that is connected to the 4-20 mA analog input, the preset temperature may not properly be
sent. If this is the case, check the current value of the analog input, and adjust the output current value of the connected 4-
20 mA signal output device.
Refer to the tables below for how to display the current value of the analog input.
Switch settings
OFF
c15
mA
SW2
SW3
-10
5
6
7
8
9
10
OFF
OFF
OFF
OFF
ON
ON
Item that can monitor
Item
code
Unit
Current value of analog
signal input
Summary of Contents for CRHV-P600YA-HPB
Page 1: ......
Page 7: ...CONTENTS HWE1312A GB ...
Page 9: ... 2 HWE1312A GB ...
Page 19: ... 12 HWE1312A GB ...
Page 41: ... II Restrictions 34 HWE1312A GB ...
Page 43: ... 36 HWE1312A GB ...
Page 51: ... III Unit Components 44 HWE1312A GB ...
Page 52: ... 45 HWE1312A GB IV Remote Controller 1 Using the Remote Controller 47 2 Function Settings 52 ...
Page 53: ... 46 HWE1312A GB ...
Page 61: ... IV Remote Controller 54 HWE1312A GB ...
Page 62: ... 55 HWE1312A GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 57 ...
Page 63: ... 56 HWE1312A GB ...
Page 67: ... V Electrical Wiring Diagram 60 HWE1312A GB ...
Page 69: ... 62 HWE1312A GB ...
Page 73: ... VI Refrigerant Circuit 66 HWE1312A GB ...
Page 75: ... 68 HWE1312A GB ...
Page 107: ... VII Control 100 HWE1312A GB ...
Page 109: ... 102 HWE1312A GB ...
Page 117: ... 110 HWE1312A GB ...
Page 165: ... IX Troubleshooting 158 HWE1312A GB ...
Page 166: ... 159 HWE1312A GB X Attachments 1 R410A saturation temperature table 161 ...
Page 167: ... 160 HWE1312A GB ...
Page 170: ......