[
II
Restrictions ]
- 33 -
HWE1312A
GB
6. Minimum and maximum water flow rates
A low flow rate will not only compromise the performance of the unit but also increase the water temperature difference be-
tween the periods when the unit is in operation and when the unit is stopped. A high flow rate will cause the pipes to corrode.
Adjust the circulating flow rate so that the difference between the inlet and outlet temperatures will be between 3 ºC and 10
ºC. Refer to the table below for the standard, minimum, and maximum flow rates.
The hot water flow rate will be considered appropriate if the difference between the inlet and outlet water temperatures is be-
tween 3 ºC and 10 ºC.
If the temperature difference is less than 3 ºC
Decrease the flow rate.
If the temperature difference is more than 10 ºC
Increase the flow rate. Check the pipes for air pockets, and make sure that the pump has enough capacity to sustain appro-
priate water pressure in a given water circuit.
7. Maintaining the appropriate amount of water in the water circuit.
(1) Amount of water in the water circuit
Shortage of water in the circulating water circuit may shorten the operation time of the unit or cause large fluctuations of water
temperature. The table below shows the minimum allowable amount of water in the water circuit. If the piping length is too
short to secure this amount, install a cushion tank to ensure that the circuit has enough water in it.
(2) Calculating the amount of water in the circuit
The amount of water in the circuit can be obtained using the following formula.
Amount of water in the water circuit = Amount of water in the water Amount of water in the unit + and Amount of water
in the load-side or heat source unit
The table below shows the amount of water in the water piping per 1 m
Amount of water in the piping
The table below shows the amount of water in the unit.
Amount of water in the unit
8. Sizes and the material types of the pipes on the unit
The table below shows the sizes of the pipes.
Pipe sizes
Standard, Minimum, and Maximum flow rates
Unit: m
3
/h
CRHV-P600YA-HPB
Standard flow rate (50Hz)
Minimum allowable flow
rate
Maximum allowable flow
rate
Heating
Hot water side
10.3
3.2
15.0
Heat source side
14.7
4.5 (counter flow)
16.0
2.0 (parallel flow)
Model
Minimum allowable amount of hot water (
ℓ
)
Minimum allowable amount of heat source (
ℓ
)
CRHV-P600YA-HPB
550
390
Pipe size
3/4B (20A)
1B (25A)
1 1/4B (32A) 1 1/2B A(40A)
2B (50A)
1 1/2B (65A)
Internal volume per meter (
ℓ
/m)
0.37
0.60
0.99
1.36
2.20
3.62
Model
Hot water side (
ℓ
)
Heat source side (
ℓ
)
CRHV-P600YA-HPB
15
10
Model
Hot water side
Heat source side
CRHV-P600YA-HPB
R2 male thread pipe <SUS304>
R2 male thread pipe <SUS304>
Summary of Contents for CRHV-P600YA-HPB
Page 1: ......
Page 7: ...CONTENTS HWE1312A GB ...
Page 9: ... 2 HWE1312A GB ...
Page 19: ... 12 HWE1312A GB ...
Page 41: ... II Restrictions 34 HWE1312A GB ...
Page 43: ... 36 HWE1312A GB ...
Page 51: ... III Unit Components 44 HWE1312A GB ...
Page 52: ... 45 HWE1312A GB IV Remote Controller 1 Using the Remote Controller 47 2 Function Settings 52 ...
Page 53: ... 46 HWE1312A GB ...
Page 61: ... IV Remote Controller 54 HWE1312A GB ...
Page 62: ... 55 HWE1312A GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 57 ...
Page 63: ... 56 HWE1312A GB ...
Page 67: ... V Electrical Wiring Diagram 60 HWE1312A GB ...
Page 69: ... 62 HWE1312A GB ...
Page 73: ... VI Refrigerant Circuit 66 HWE1312A GB ...
Page 75: ... 68 HWE1312A GB ...
Page 107: ... VII Control 100 HWE1312A GB ...
Page 109: ... 102 HWE1312A GB ...
Page 117: ... 110 HWE1312A GB ...
Page 165: ... IX Troubleshooting 158 HWE1312A GB ...
Page 166: ... 159 HWE1312A GB X Attachments 1 R410A saturation temperature table 161 ...
Page 167: ... 160 HWE1312A GB ...
Page 170: ......