13. OUTDOOR INSTALLATION
Hyper Heating Inverter R2-Series
In case of collective installation and continuous installation
• When installing multiple units, make sure to take into consideration factors such as providing enough space for people to pass through,
ample space between blocks of units, and sufficient space for airflow. (The areas marked with [A] in the figures below must be left open.)
• In the same way as with the single unit installation, add the dimension that exceeds the height limit (shown as "h1" through "h3" in the figures) to L1, L2,
and L3 as shown in the tables below.
• If there are walls in the front and rear of the block of units, up to six units can be installed consecutively side by side, and a space of 1000 mm (39-3/8 in)
or more must be left between each block of six units.
(1) Side-by-side installation
[mm (in)]
When the distances between the units (L4) need to
be small
When the distance behind the block of units (L2) needs
to be small
When there are walls in the front and rear of the
block of units
When there is a wall on either the right or left side of the
block of units
When there are walls in the front and rear of the
block of units
When there are two walls in an L-shape
(2) Face-to-face installation
(3) Combination of face-to-face and side-by-side installations
Unit height
Unit height
Unit height
Unit height
Unit height
Unit height
Unit height
[A]
[A]
[A]
[A]
[A]
Required minimum distance [mm (in)]
L1 (Front)
L2 (Rear)
L4 (Between)
450 (17-3/4) + h1
450 (17-3/4) + h2
30 (1-3/16)
Required minimum distance [mm (in)]
L1 (Front)
L2 (Rear)
L4 (Between)
450 (17-3/4) + h1
300 (11-13/16) + h2
450 (17-3/4)
[A]
[A]
[A]
h3
L4
L3
L4
Required minimum distance [mm (in)]
L1 (Front)
L2 (Rear)
L4 (Between)
450 (17-3/4) + h1
300 (11-13/16) + h2
450 (17-3/4)
Required minimum distance [mm (in)]
L3 (Right/Left)
L4 (Between)
30 (1-3/16) + h3
450 (17-3/4)
Required minimum distance [mm (in)]
L2 (Rear)
L2' (Rear)
L4 (Between)
450 (17-3/4) + h2
450 (17-3/4) + h2'
900 (35-7/16)
Required minimum distance [mm (in)]
L2 (Rear)
L3 (Right/Left)
L4 (Between)
450 (17-3/4) + h2
1000 (39-3/8) + h3
900 (35-7/16)
[A]: Leave open in two directions.
h2
L2
L1
h1
L4
h2
h1
L1
L2
L4
h1
h2
L1
L4
L4
L2
h2
L2’
L4
L2
h2’
Unit height
Unit height
Unit height
Unit height
[A]
[A]
h2
L2
L4
L3
h3