12. PIPING DESIGN
Hyper Heating Inverter R2-Series
The above calculation result of the amount of refrigerant to be charged must become below the value in the table below.
Total index of the outdoor units
HP72
HP96
HP120
HP144
T/YNU
T/YNU
T/YNU
T/YSNU
Maximum refrigerant charge
Factory charged
17 lbs
10 oz
23 lbs
12 oz
23 lbs
12 oz
35 lbs
5 oz
Charged on site
56 lbs
4 oz
67 lbs
11 oz
80 lbs
15 oz
93 lbs
12 oz
Total for system
73 lbs
14 oz
91 lbs
8 oz
104 lbs
12 oz
128 lbs
16 oz
Factory charged
8.0kg
10.8kg
10.8kg
16.0kg
Charged on site
25.5kg
30.7kg
36.7kg
42.5kg
Total for system
33.5kg
41.5kg
47.5kg
58.5kg
47 lbs
10 oz
115 lbs
9 oz
163 lbs
3 oz
47 lbs
10 oz
150 lbs
13 oz
198 lbs
7 oz
HP192
T/YSNU
HP240
T/YSNU
21.6kg
52.4kg
74.0kg
21.6kg
68.4kg
90.0kg
Limitation of the amount of refrigerant to be charged