MEES19K180
PURY-H
P-
T(
S)NU-
A, Y(S)
NU-A
5
1. SPECIFICATIONS
Hyper Heating Inverter R2-Series
Outdoor Model
PURY-HP144TSNU-A
Indoor Model
Non-Ducted
Ducted
Power source
3-phase 3-wire 208-230 V ±10% 60 Hz
Cooling capacity
*1 BTU/h
144,000
(Nominal)
kW
42.2
Power input
kW
11.92
(208-230) Current input
A
36.7-33.2
(Rated)
BTU/h
138,000
kW
40.4
Power input
kW
10.73
11.34
(208-230) Current input
A
33.0-29.9
34.9-31.6
Temp. range of
Indoor
W.B.
59~75°F (15~24°C)
cooling
Outdoor
D.B.
23~126°F (-5~52°C)
Heating capacity
*2 BTU/h
160,000
(Nominal)
kW
46.9
Power input
kW
12.50
(208-230) Current input
A
38.5-34.8
(Rated)
BTU/h
152,000
kW
44.5
Power input
kW
11.22
11.91
(208-230) Current input
A
34.6-31.2
36.7-33.2
Temp. range of
Indoor
D.B.
59~81°F (15~27°C)
heating
Outdoor
W.B.
-22~60°F (-30~15.5°C)
Indoor unit
Total capacity
50~150% of outdoor unit capacity
connectable
Model/Quantity
P04~P96/1~36
Sound pressure level (measured in anechoic room) *3 dB <A>
59.5/61.0
Sound power level (measured in anechoic room) *3
dB <A>
78.5/80.0
Refrigerant
High pressure
in. (mm)
7/8 (22.2) Brazed
piping diameter
Low pressure
in. (mm)
1-1/8 (28.58) Brazed
Set Model
Model
PURY-HP72TNU-A
PURY-HP72TNU-A
Minimum Circuit Ampacity
A
38-35
38-35
Maximum Overcurrent Protection
A
60-50
60-50
FAN
Type x Quantity
Propeller fan x 2
Propeller fan x 2
Airflow rate
cfm
7,400
7,400
m
3
/min
210
210
L/s
3,500
3,500
Control, Driving mechanism
Inverter-control, Brushless DC motor
Inverter-control, Brushless DC motor
Motor output
kW
0.46+0.46
0.46+0.46
*4 External static press.
0 in.WG (0 Pa)
0 in.WG (0 Pa)
Compressor
Type x Quantity
Inverter scroll hermetic compressor x 1
Inverter scroll hermetic compressor x 1
Manufacture
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method
Inverter
Inverter
Motor output
kW
4.0
4.0
Case heater
kW
-
-
Lubricant
MEL46
MEL46
External finish
Pre-coated galvanized steel sheet
Pre-coated galvanized steel sheet
<MUNSELL 5Y 8/1>
<MUNSELL 5Y 8/1>
External dimension H x W x D
in.
71-5/8 x 49-1/4 x 29-3/8
71-5/8 x 49-1/4 x 29-3/8
mm
1,818 x 1,250 x 745
1,818 x 1,250 x 745
Protection
High pressure protection
High pressure sensor, High pressure switch at 4.15 MPa (601
psi)
High pressure sensor, High pressure switch at 4.15 MPa (601
psi)
devices
Inverter circuit (COMP./FAN)
Over-heat protection, Over-current protection
Over-heat protection, Over-current protection
Fan motor
-
-
Refrigerant
Type x original charge
R410A x 17 lbs + 10 oz (8.0 kg)
R410A x 17 lbs + 10 oz (8.0 kg)
Control
Indoor LEV and BC controller
Net weight
lbs (kg)
609 (276)
609 (276)
Heat exchanger
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
-
-
Pipe between unit and High pressure
in. (mm)
5/8 (15.88) Brazed
5/8 (15.88) Brazed
distributor
Low pressure
in. (mm)
3/4 (19.05) Brazed
3/4 (19.05) Brazed
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
Drawing
External
KB94C0GZ
Wiring
KE94G811
KE94G811
Standard
Document
Installation Manual
attachment
Accessory
Details refer to External Drw
Optional parts
Outdoor Twinning kit: CMY-R100NCBK
joint: CMY-Y102SS-G2,CMY-Y102LS-G2,CMY-R160-J1,CMY-R201,202,203,204,306S-G,CMY-R302,303,304,305S-G1
Main BC controller: CMB-P108,1012,1016NU-JA1,CMB-P1016NU-KA1
Sub BC controller: CMB-P104,108NU-KB1
Remarks
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Notes:
Unit converter
1.Nominal cooling conditions (Test conditions are based on AHRI 1230)
Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Nominal heating conditions (Test conditions are based on AHRI 1230)
Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.Cooling mode/Heating mode
4.External static pressure option is available (0.12 in.WG, 0.24 in.WG, 0.32 in.WG/30 Pa, 60 Pa, 80 Pa).
BTU/h
=kW x 3,412
cfm
=m
3
/min x 35.31
lbs
=kg/0.4536
*Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice.
subject to rounding variation.
0000005744.BOOK 5 ページ 2020年2月25日 火曜日 午後5時19分