MEES19K180
PURY-HP-T(S)NU-A, Y(S)NU-A
116
13. OUTDOOR INSTALLATION
Hyper Heating Inverter R2-Series
13-2. Spacing
(1) When all walls are within their height limits*.
(2) When one or more walls exceed their height limits*.
When the wall(s) at the front and/
or the right/left exceed(s) their
height limits
Add the dimension that exceeds the height limit (shown as "h1" through "h3" in the figures) to L1, L2, and L3 as shown in the
table below.
When the wall at the rear exceeds
its height limit
When all walls exceed their height
limits
(3) When there are overhead obstacles
In case of single installation
≤ Unit height
≤ Unit height
Unit height
Unit height
Unit height
Unit height
Unit height
Unit height
Unit height
≤ Unit height
≥ 240 (9-1/2)
≥45°
≥ 50 (2)
≥ 1000 (39-3/8)
Air outlet guide
(not supplied)
L1
L2
L3
[mm (in)]
* Height limit
Front/Right/Left/Rear Same height or lower than the overall height of the unit
Required minimum distance [mm (in)]
L1 (Front)
L2 (Rear)
L3 (Right/Left)
When the distance behind the unit (L2) needs to be small
450 (17-3/4)
300 (11-13/16)
450 (17-3/4)
When the distance to the right or left (L3) needs to be small
450 (17-3/4)
450 (17-3/4)
30 (1-3/16)
≤ Unit height
≤ Unit height
Required minimum distance [mm (in)]
L1 (Front)
L2 (Rear)
L3 (Right/Left)
When the distance behind the unit (L2) needs to be small
450 (17-3/4) + h1
300 (11-13/16) + h2
450 (17-3/4) + h3
When the distance to the right or left (L3) needs to be small
450 (17-3/4) + h1
450 (17-3/4) + h2
30 (1-3/16) + h3
h3
L1
L2
L3
h1
h2
L1
L2
L3
h2
L1
h3
h2
L2
L3
L3
h1
0000005744.BOOK 116 ページ 2020年2月25日 火曜日 午後5時19分