11. M-NET CONTROL
Hyper Heating Inverter R2-Series
Table 2 The equivalent power supply
*1 When one or more indoor units listed below is connected, subtract 3 from the equivalent power supply.
*2 If PAC-SC51KUA is used to supply power at TB7 side, no power supply need from Outdoor/Heat source unit at TB7, Connector TB3 itself will therefore
have 32.
With the equivalent power consumption values and the equivalent number of units in Table 1 and Table 2, PAC-SF46EPA-G
can be designed into the air-conditioner system to ensure proper system communication according to (A), (B), (C).
(A) Firstly, count from TB3 at TB3 side the total equivalent number of units of Indoor units, ME remote controller, and
System controllers. If the total equivalent number of units reaches 40, a PAC-SF46EPA-G should be set.
(B) Secondly, count from TB7 side to TB3 side the total transmission power consumption. If the total equivalent power
supply reaches 32, a PAC-SF46EPA-G should be set. Yet, if a PAC-SC51KUA or another controller with a built-in pow-
er supply, such as PAC-YG50ECA, is used to supply power at TB7 side, count from TB3 side only.
(C) Thirdly, count from TB7 at TB7 side the total transmission power consumption, If the total equivalent power supply for
only TB7 reaches 6, a PAC-SF46EPA-G should be set. Also, count from TB7 at TB7 side the total equivalent number
of units of System controllers, and so on. If the total equivalent number of units reaches 40, a PAC-SF46EPA-G should
be set.
* The equivalent power supply of S-Series outdoor unit is 12.
* When one or more indoor units listed in Table 3 is connected, subtract 3 from the equivalent power supply.
Category
Model
The equivalent
power supply
Transmission Booster
PAC-SF46EPA-G
25 *1
Power supply unit
PAC-SC51KUA
5
Expansion controller
PAC-YG50ECA
6
BM ADAPTER
BAC-HD150
6
System controller
AE-200A/AE-50A
0.75
EW-50A
1.5
LM-AP
0
Outdoor/Heat source unit
TB3 and TB7 total
TB7 only
TB3 only
Outdoor unit other than the following
units *2
32 *1
6
32*1 - equivalent power
supplied to TB7
S-Series outdoor unit
12 *1
0
12 *1
TLMU/TKMU outdoor unit
32 *1
- *3
32 *1
Table 3
Category
Model
Indoor unit
Sized P72, P96
PEFY-AF1200CFM(R)-E
System example
ME remote
controller
ME remote
controller
Lossnay
unit
Lossnay
unit
02
01
N1
N3
N2
N4
Within N4, the total equivalent transmission
power consumption should not exceed 25.
TB7
TB3
TB7
TB3
Transmission booster (No.2) should be used,
if the total equivalent transmission power consumption reaches 5.
PAC-SF46EPA
TRANSMISSION BOOSTER
3.4kg
220-240V:0.7A ~/N
WEIGHT
POWER RATING
MODEL
MADE IN JAPAN
50
UP
PAC-SF46EPA
TRANSMISSION BOOSTER
3.4kg
220-240V:0.7A ~/N
WEIGHT
POWER RATING
MODEL
MADE IN JAPAN
50
UP
Transmission
booster
(No.1)
Transmission
booster
PAC-SF46EPA-G
(No.2)
Centralized controller
(AE-200A)
Outdoor/Heat source unit
Transmission booster (No.1) should be used, if the total equivalent number of
units of Indoor units and ME remote controllers reaches 40,
or if the total equivalent transmission power consumption reaches 32.
Within N2, conditions 1,2 should be followed.
1.The total equivalent number of units of Indoor units
and ME remote controller should not exceed 40.
2.The total equivalent transmission power consumption
should not exceed 25.
Lossnay
remote controller
Lossnay
remote controller
0000005744.BOOK 85 ページ 2020年2月25日 火曜日 午後5時19分