11. M-NET CONTROL
Hyper Heating Inverter R2-Series
11-4-3-4. ME remote controller, Single-refrigerant-system, No system controller
2. Address should be set to Indoor units, system controller and ME remote controllers.
3. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME R/C consume the M-NET power for transmission
use. The power balance is needed to consider for long M-NET wiring. Details refer to
11-3. "System configuration restrictions".
NOTE:
1. Outdoor units OC and OS in one refrigerant circuit system are automatically detected.
OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their
address.
Indoor unit
ME R/C
ME R/C ME R/C
01
BC controller
53
02
03
04
05
TB5
TB02
TB5
TB5
102
ME R/C
104
105
155
TB5
TB5
ME R/C
101
Group 2
Group 1
Group 3
Group 4
TB3
TB3
52
51
OC
OS
TB3
51
OC
CN41
CN40
CN41
CN40
CN41
CN40
OFF
DipSW5-1
OFF
DipSW5-1
OFF
DipSW5-1
<Two outdoor units>
<One outdoor unit>
4. Indoor units should be set with a branch number.
11-4-3-5. ME remote controller, Single-refrigerant-system, System controller, Lossnay
2. Address should be set to Indoor units, Lossnay central controller, ME remote controllers.
3. For a system having more than 32 indoor unit, confirm the need of Booster at
11-3. "System configuration restrictions".
NOTE:
ME R/C ME R/C
Indoor unit
ME R/C
104
105
155
01
04
05
TB5
TB5
TB5
ME R/C
101
Group 1
Group 3
Group 4
201
SC
*SC can be connected to TB3 side or TB7 side;
Should SC connected to TB7 side, change Jumper from CN41 to CN40 at the Outdoor unit module so as to supply power to the SC.
Up to three System controllers can be connected to TB3 side.
1. Outdoor units OC and OS in one refrigerant circuit system are automatically detected.
OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their
address.
<Two outdoor units>
<One outdoor unit>
TB3
TB3
52
51
OC
OS
TB3
51
OC
CN41
CN40
CN41
CN40
CN41
CN40
ON
DipSW5-1
ON
DipSW5-1
ON
DipSW5-1
4. Indoor units should be set with a branch number.
BC controller
53
TB02
PURY
PURY
PURY
PURY
ME R/C
102
02
03
TB5
Lossnay
Interlocked with
M-NET address 02
TB5
Group 2