MEES19K180
PURY-H
P-
T(
S)NU-
A, Y(S)
NU-A
15
2. EXTERNAL DIMENSIONS
Hyper Heating Inverter R2-Series
PURY-HP72, 96, 120TNU-A
Unit: mm (in.)
1.Required space around the unit
2.Foundation work
Front
Front
<T
op view>
<Unit:mm(in)>
<T
op view>
<T o be left open>
Front
W
all <H>
<T
o be left open>
Front
<Unit:mm(in)>
W
all <H>
<T o be left open>
<T o be left open>
<T o be left open>
Front
W
all <H>
W
all <H>
Wa
ll <H>
Wa
ll <H>
Front
Front
<T
o be left open>
W
all <H>
Front
W
all <H>
<T o be left open>
<T o be left open>
Front
Front
Front
W
all <H>
W
all <H>
Front
<T o be left open>
<T
o be left open>
<W
all height limit> Front
:Up to the unit height
Back :Up to the unit height
Side
:Up to the unit height
M10 anchor bolt
<field supply required>
Fixing plate
<field supply required>
Fig.A
<Side view>
Front
Fig.B
●In case of single installation
1 Secure enough space around the unit as shown in the figure below
.
· With a space of at least
2 When the height of the walls on the front, back or on the sides<H>
exceeds the wall height limit as defined below
add the height that exceeds the height limit <h> to the figures that
are marked with an asterisk.
1
Ta
ke into consideration the surface strength, water drainage route,
piping route, and wiring route when preparing the installation site.
<Note that the drain water comes out of the unit during operation.>
2 Build the foundation in such way that the corner of the installation leg is
securely supported as shown in the right figure.(Fig.A)
When using a rubber isolating cushion, please ensure it is large enough
to cover the entire width of each of the unit's legs.
3
The protrusion length of the anchor bolt must not exceed 30mm(1-3/16).(Fig.A)
4 Use four fixing plates as shown in the right figure <field supply required>
when using post-installed anchor bolts.(Fig.B)
5
To
prevent small animals and water and snow from entering the unit and damaging its parts,
close the gap around the edges of through holes for pipes and wires with
filler plates <field supply required>.
6 When the pipes or cables are routed at the bottom of the unit,
make sure that the through hole at the base of the unit does not get blocked
with the installation base.
7 Refer to the Installation Manual when installing units on an installation base.
●In case of collective installation
1 When multiple units are installed adjacent to each other
, secure enough space to allow
for air circulation and walkway between groups of units as shown in the figures below
.
2
At least two sides must be left open.
3
As with the single installation, add the height that exceeds the height limit<h>
to the figures that are marked with an asterisk.
4 If there is a wall at both the front and the rear of the unit, install up to six units
consecutively in the side direction and provide a space of 1000mm(39-3/8) or more as inlet space/
passage space for each six units.
450mm(17-3/4) to the wall
on the back of the unit
· With a space of at least
300mm(1
1-13/16) to the wall
on the back of the unit
30 min.*
450 min.*
450 min.*
300 min.*
450 min.*
450 min.*
450 min.
30 min.
450 min.
450 min.*
450 min.
300 min.*
450 min.*
300 min.*
450 min.*
1000 min.*
900 min.
450 min.*
900 min.
450 min.*
450 min.*
30 min.*
450 min.
450 min.
450 min.*
450 min.*
30 min.*
(1-3/16)
(1-3/16)
(17-3/4)
(17-3/4)
(17-3/4)
(17-3/4)
(17-3/4)
(11-13/16)
(17-3/4)
(17-3/4)
(1-3/16)
(17-3/4)
(17-3/4)
(1-3/16)
(39-3/8)
(17-3/4)
(35-7/16)
(17-3/4)
(17-3/4)
(17-3/4)
(11-13/16)
(17-3/4)
(17-3/4)
(17-3/4)
(1
1-13/16)
(35-7/16)
(17-3/4)
30mm max.
Unit height
h
H
Unit height
h
H
(1-3/16)
0000005744.BOOK 15 ページ 2020年2月25日 火曜日 午後5時19分