13. OUTDOOR INSTALLATION
Hyper Heating Inverter R2-Series
13-4. Weather countermeasure
13-5. Countermeasure to wind
Referring to the figure shown below, take appropriate measures which will suit the actual situation of the place for installation.
A unit installed alone is vulnerable to strong winds. Select the installation site carefully to minimize the effect of winds.
To install a unit in a place where the wind always blows from the same direction, install the unit so that the outlet faces away
from the direction of the wind.
Prevention the Outdoor unit from wind and snow damages in cold or snowy areas, snow hood shown below is recommended
and helpful.
*Do not use a snow hood made of stainless steel, which may cause the unit to rust. If the use of a stainless snow hood is the
only option, contact the sales office before installing it.
• Snow hood
Countermeasure to snow and wind
In cold and/or snowy areas, sufficient countermeasures to wind and snow damages should be taken for operating unit in normal
and good condition in winter time. Surround the units with snow nets or fences to protect them from snow. Even in the other areas,
full consideration is required for installation of unit in order to prevent abnormal operations caused by wind or snow.
When rain
and snow directly fall on unit in the case of air-conditioning operations in 10 or less degrees centigrade outdoor air
(50 or less degrees fahrenheit outdoor air) , mount inlet and outlet ducts on unit for assuring stable operations.
It is recommended to install a duct to fully make use of the advantages of the panel heater.
Outlet
Inlet
Snow hood
Raised base
A
C
C
C
C
D
D
D
C
C
C
A
B
B
B
B
B
<Front view>
<Side view>
Wind
Install the outdoor unit where seasonal
winds do not blow directly against the
unit, such as behind a building.
Install the outdoor unit to avoid having
seasonal winds against the front of air
outlet/inlet on the unit.
A
A
A
A
0000005744.BOOK 123 ページ 2020年2月25日 火曜日 午後5時19分