8. CAPACITY TABLES
Hyper Heating Inverter R2-Series
8-4-3. How to obtain the equivalent piping length
1. PURY-HP72TNU/YNU
Equivalent length = (Actual piping length to the farthest indoor unit ) + (1.15 x number of bent on the piping) [ft.]
Equivalent length = (Actual piping length to the farthest indoor unit ) + (0.35 x number of bent on the piping) [m]
2. PURY-HP96TNU/YNU
Equivalent length = (Actual piping length to the farthest indoor unit ) + (1.38 x number of bent on the piping) [ft.]
Equivalent length = (Actual piping length to the farthest indoor unit ) + (0.42 x number of bent on the piping) [m]
3. PURY-HP120TNU/YNU
Equivalent length = (Actual piping length to the farthest indoor unit ) + (1.64 x number of bent on the piping) [ft.]
Equivalent length = (Actual piping length to the farthest indoor unit ) + (0.50 x number of bent on the piping) [m]
4. PURY-HP144TSNU/YSNU
Equivalent length = (Actual piping length to the farthest indoor unit ) + (1.64 x number of bent on the piping) [ft.]
Equivalent length = (Actual piping length to the farthest indoor unit ) + (0.50 x number of bent on the piping) [m]
5. PURY-HP192TSNU/YSNU
Equivalent length = (Actual piping length to the farthest indoor unit ) + (1.64 x number of bent on the piping) [ft.]
Equivalent length = (Actual piping length to the farthest indoor unit ) + (0.50 x number of bent on the piping) [m]
6. PURY-HP240TSNU/YSNU
Equivalent length = (Actual piping length to the farthest indoor unit ) + (1.64 x number of bent on the piping) [ft.]
Equivalent length = (Actual piping length to the farthest indoor unit ) + (0.50 x number of bent on the piping) [m]