(2) Setting the sensor type
Pressing the [Sensor type selection] button will display the screen as shown below.
(a) Sensor type selection button
Select between [Temperature sensor] and [Humidity sensor].
Selecting [Temperature sensor] will automatically select ºC as the measurement unit, and selecting [Humidity sensor] will automatically
select % as the measurement unit.
(b) Lower limit button
Set the upper and lower limits for the measurement range.
Press the [Lower limit] button to call up the on-screen keypad, set the lower limit, and press the [OK] button to set the lower limit.
The settable range for the temperature sensor is between -100.0ºC (-148.0ºF) (lower limit) and +99.9ºC (211.9ºF) (upper limit).
The settable range for the humidity sensor is between 0.0% (lower limit) and 99.9% (upper limit).
(c) Upper limit button
Set the upper limit in the same manner.
(d) Correction value button
Enter the correction value in the same manner as setting the lower limit value, using the [Correction value] button.
Enter the correction value when the measurement values need to be corrected for the difference between the sensor reading and the
actual value.
The settable range is between -10ºC and +10ºC (-18.0ºF and +18.0ºF ).
(a) Sensor type
selection button
(c) Upper limit button
(b) Lower limit button
(d) Correction value
button
Temperature Sensor
Humidity Sensor
Value display window
Keypad