Operation
*1
External input
Connects to an external input/output device that stops the units in an emergency, run or stop the
units, permit or prohibit the operation of units collectively. Requires an external input/output
adapter (sold separately).
Monitor
*1
ON/OFF (system)
The ON/OFF indicator lamp (LED) indicates if one or more groups or all the groups in the system
are stopped. (Not applicable to a general equipment.)
Operation status of each group in
the system
Operation status (ON/OFF), operation mode, fan speed, temperature setting, air flow direction, and
operation status (ON/OFF) of interlocked units are displayed.
Operation status of each group in
the system (HWHP (CAHV))
Operation status (ON/OFF), operation mode, temperature setting, fan mode, and temperature
(Representative, Outdoor, Inlet, Outlet) are displayed.
Operation status of each group in
the system (measurement)
Measurements by the temperature sensor and humidity sensor that are connected to the AI
controller are displayed.
Measurements by the watt-hour meter that is connected to the PI controller are displayed.
Filter sign
Indicates that the filters on the units in a given group is due for cleaning.
Water circuit sign
(Air To Water (PWFY))
Indicates that the circulating water circuit in a given group is due for replacement.
Local operation prohibition
Displays the functions that the controller forbids or the functions that are forbidden by High-level
equipment.
Error
The address of the unit in error, error code, and the address of the unit that detected the error will
appear.
Error history monitor
Up to 384 errors can be stored in memory. (128 errors per AG-150A or Expansion controller (64 unit
errors, 64 communication errors))
External output
Outputs signals (run/stop, error) to an external device. Requires an external input/output adapter
(sold separately).
Initi
al Sett
ings Operation
*1
Date and time
This function is used to set the current date/time and daylight savings time.
License
This function is used to register license.
Unit Info.
This function is used to set unit name, ID number, connection or non-connection of Expansion
controller, brightness of the LCD, sound volume, date format, time format, temperature unit, and
display language, test run availability, screen lock and room temperature availability.
Network
This function is used to set the IP address, subnet mask address, and gateway settings for the LAN
and also to set the address, K-transmission converter address, local control prohibit settings, and
external input settings for the M-NET; and the Expansion controller settings.
Advanced
Allows the Time Master/Sub setting to be made.
Enables/disables the Seasonal schedule settings.
Groups
This function is used to register indoor units, LOSSNAY units , DIDO controller (PAC-YG66DCA),
Air To Water (PWFY), HWHP (CAHV), remote controllers, and lower-level system controllers to a
group.
Blocks
This function is used to register a group to a block.
Interlock
This function is used to interlock the operation of indoor units and LOSSNAY units.
Floor Layout
This function is used to make the basic settings for the floor layout and display position of the
groups.
Measurement
Temperature sensor and humidity sensor settings can be set by connecting an AI controller.
Watt-hour meter and water meter settings can be set by connecting a PI controller.
Monitor
*1
Refrigerant system configuration
confirmation
Allows the user to see which indoor units are connected to each outdoor unit.
Operation
*1
Ext Temp Interlock
Control level of outside temperature interlock function can be set for each group.
Setback
Control time and upper/lower limit temperature can be set for setback function.
User Info
Maintenance User
Allows the maintenance user name and password to be set.
Building Manager
Allows the building manager name, password, function enable/disable settings to be made.
Maintenance
Backup
The setting data (Initial setting and user info) can be copied to a USB memory drive.
Import
The setting data (Initial setting and user info) can be read from a USB memory drive.
CSV output
Up to 62 days of the operational data (charge parameters and power consumption data) can be
stored to a USB memory.
Touch panel calibration
The touch position on the touch panel can be adjusted.
Other
Data
back-up
Connection/Interlock Information
Group setting information and interlock setting information are retained, even if power is turned off.
Error history
Retained, even if power is turned off.
Schedule data
Schedule information of each group is retained, even if power is turned off.
Current time
Current time is retained by the built-in capacitor for a week, even if power is turned off.
(It takes approximately a day to fully charge the built-in capacitor. There is no need to replace the
capacitor.)
Saving the data on a USB drive
The initial setting data, user info, and operational data (charge parameters, power consumption)
can be stored to a USB memory.
Reading data from USB memory
Initial setting data can be read from USB memory.
Device
maintenance
Screen lock function
The screen can be locked to prevent access until a valid user name and password are entered.
Touch panel cleaning
Touch panel is locked and can be cleaned.
Time synchronization
Clocks on the controllers and units that are under the control of the main controller are synchronized
once a day (applicable only to the ones that support this function).
Function
Description